Troubleshooting tips, Recovery and vacuum operation – Robinair 34134-2K Refrigerant Recovery, Recycle, Recharge Unit User Manual
Page 16

14
© 2000 Robinair, SPX Corporation
Troubleshooting Tips
RECOVERY AND VACUUM OPERATION
Compressor does not start or stop prematurely
Problem:
No power.
Solution:
Check for power at plug or outlet.
Problem:
**OVERLOAD** is displayed.
Solution:
Move refrigerant from unit tank to approved refrigerant storage
tank. See RECHARGING A/C SYSTEM.
Problem:
HIGH PRESSURE is displayed.
Solution:
Be sure tank valves are open and hoses are correctly connected
to the unit tank.
Problem:
**SCALE** is displayed.
Solution:
The scale is damaged, disconnected, out of calibration or over-
loaded.
Runs but gauges won't indicate 13 in Hg (0.44 BAR)
Problem:
Oil drain valve open.
Solution:
Close the oil drain valve.
Problem:
Leak in vehicle system.
Solution:
Locate and repair all system leaks.
Problem:
Manifold valves not open.
Solution:
Open valves.