Reversomatic Deluxe Series User Manual
Page 9

Programming Instructions for Wall Control Unit (cont’d)
7
After pressing the MODE button,
the unit switches to Airflow 
Balancing disable/enable setting.
The current value is enabled.
(Automatic Balancing mode)
PROGRAM
Press + button. The value is 
changed to disabled. 
(Manual
Balancing mode - for units 
without built in automatic 
Electronic Air Balancing)
NO BAL
PROGRAM
Press + button again. The value 
is changed to enabled. When 
you select the desired setting,
press MODE button. The setting
is reprogrammed with the new 
value. 
After pressing the MODE button,
the unit switches to wall control
address setting. The current 
value is A1. (Wall control #1)
PROGRAM
PROGRAM
Press + button, The value is 
changed to A2. (Wall control #2)
PROGRAM
Press + button, The value is 
changed to A3 (Wall control #3). 
When you select the desired 
address, press MODE button. 
The address is reprogrammed 
with the new value.
%
OFF
After pressing the MODE button,the 
unit return back to normal operational 
made. The new programmed settings 
are stored in the memory, & the 
HRV/ERV will operate according to 
them. 
Displaying Errors
Loss of communication with the 
Control Board. HRV/ERV 
switched to OFF mode 
automatically.
OFF
Defrosting Temperature Sensor 
Failure. Blinks with the current 
operational display. HRV
does not perform defrost cycles.
/ERV
NORMAL
NORMAL
Airflow Sensor Failure. Blinks 
with the current operational 
display. HRV
runs at fixed
default Low and High fans
speeds.
/ERV
Humidity Sensor Failure. Blinks 
with the current operational 
display. HRV/ERV does not run 
in High Humidity mode. 
NORMAL
If Airflow Balancing is enabled, 
after pressing the MODE button,
the unit jumps to Wall Mount 
address setting.
Else if Airflow Balancing is 
disabled, after pressing the 
MODE button, the unit switches
to 
supply fan manual Airflow
adjustment mode.
“SF” is displayed when the unit 
is in supply fan manual 
adjustment mode.
Press + or - button to increase 
or decrease supply fan speed. 
“SF” blinks when the button is 
depressed. It may take several 
minutes to speed up or 
slow
down.
Release of + or - button stops 
supply fan speed change. 
The changed supply fan speed 
is stored in non-volatile memory
which will be used from now on 
for the current airflow settings 
(N1-N4 and H1-H4) can be 
manually changed and stored in 
non-volatile memory.
Note: Enabling of balancing 
mode will cause manual fan 
speed change back to default 
settings.
Airflow
PROGRAM
After pressing the MODE button,
the unit switches to 
exhaust fan
manual adjustment mode. “EF” 
is displayed when the unit is in 
exhaust fan manual airflow 
adjustment mode.
Press + or - button to increase 
or decrease exhaust fan speed. 
“EF” blinks when the button is 
depressed. It may take several 
minutes to speed up or 
slow
down.
Releasing of + or - button stops 
exhaust fan speed change.
PROGRAM
The changed exhaust fan speed 
is stored in non-volatile memory
which will be used from now on 
for the current airflow settings 
(N1-N4 and H1-H4) can be 
manually changed and stored in 
non-volatile memory.
Note: Enabling of balancing 
mode will cause manual fan 
speed change back to default 
settings.
NORMAL
Fans Failure. Blinks with the 
current operational display. HRV
stops fans, closes damper
& opens furnace / fan-coil / 
heat pump interlock relay.
/
ERV
(Auto balancing unit only)
Note: Default Wall Unit Address is A1. If multiple Wall units are
installed, they must have different addresses (i.e. A2,A3) in 
order to make communication work.
If the Wall Unit is in Programming mode and there is no 
button pressing for timeout period of 60 sec., the Unit 
returns automatically back in normal operational mode.
•
•
Note:
In manual balancing mode, we recommend SF & EF values
are adjusted by professional balancer or qualified contractor.
Note:- E3 & E5 will not be displayed on non-balancing unit.
 see page-14 for possible causes and solutions.
(Auto balancing unit only)
