6setting internal programming parameters – Reversomatic Deluxe Series User Manual

Page 8

background image

NOTE: There are totally 9
Defrost Maps.

Map1-3 are for

Aluminum Core (RHRV-D100A).
Map 4-6 are for Polypropylene
Core (RHRV-D100P)
. Map 7-9 are
for ERV Core (RERV-D100)
.
Factory programmed default DEFR
values are Map-1 for RHRV-D100A,
Map-4 for RHRV-D100P & Map-7
for RERV- D100.

Programming Instructions for Wall Control Unit (cont’d)

6

Setting Internal Programming Parameters

%

OFF

Mode OFF. Current Humidity
70%

Press both + and - buttons for
4 sec. Unit switches to
Programming Mode. The first
programming parameter is the
High Ventilation Timeout Timer.
The current value is 0, which
means timer is off.

TIMER

PROGRAM

Press + button. Timeout Timer
changes to 1 hour.

TIMER

PROGRAM

TIMER

PROGRAM

Press + again. Timeout Timer
changes to 2 hours.

TIMER

PROGRAM

Press + again. Timeout Timer
changes to 3 hours. When you
select the desired timeout (0-3),
press the MODE button. Time-
out timer is reprogrammed with
the new value.
NOTE: Factory programmed
default TIMER value 0.

DEFR

PROGRAM

After pressing the MODE button,
the unit switches to Defrost Map
selection. The current Defrost
map is #1.

DEFR

PROGRAM

Press + button, Defrost Map
changes to #2.

DEFR

PROGRAM

Press + button, Defrost Map
changes to #3.

DEFR

PROGRAM

Press + button, Defrost Map
changes to #4. When you select
the desired Defrost Map # (1-9),
press MODE button. Defrost
Map is reprogrammed with the
new number.

%

PROGRAM

NO BAL
TIMER
DEFR
SET

REMOTE

NORMAL

HIGH

RECIRC

ENER SAVE

OFF

After pressing the MODE button,
the unit switches to Normal
Mode Airflow setting. The current
value is n1. (which gives you
app. 63 CFM).

PROGRAM

NORMAL

Press + button. The value is
changed to n2. (that gives you
app. 75 CFM).

PROGRAM

NORMAL

PROGRAM

Press + button. The value is
changed to n4. (which gives you
app. 95 CFM).

When you select the desired
setting for Normal Mode airflow
(n1 to n4), press MODE button.
The Normal Mode Airflow setting
is reprogrammed with the new
value.
NOTE: Factory programmed
default value n2.

NORMAL

After pressing the MODE
button, the unit switches to High
Ventilation Mode Airflow setting.
The current value is H1 (which
gives you

app. 80 CFM).

HIGH

PROGRAM

PROGRAM

NORMAL

Press + button. The value is
changed to n3. (gives you

app.

84 CFM).

Press + button. The value is
changed to H2 (which gives you
app. 100 CFM).

HIGH

PROGRAM

HIGH

PROGRAM

Press + button. The value is
changed to H3 (which gives you
app. 125 CFM).

HIGH

PROGRAM

Press + button. The value is
changed to H4 (which gives you
app. 155 CFM).

When you select the desired
setting for High Ventilation Mode
airflow (H1 to H4), press MODE
button. The High Ventilation
Mode Airflow setting is
reprogrammed with the new
value.
NOTE: Factory programmed
value H2.

After pressing the MODE button,
the unit switches to Defrost cycle
mode selection. The current
Defrost cycle mode is
recirculation ( ).

PROGRAM

DEFR

Press + button. Defrost cycle
mode changes to fan cycle ( ).
When you select the desired
defrost cycle mode, press MODE
button.Defrost cycle mode is
reprogrammed w/ the new value.

NOTE:

default is recirculation defrost

Factory programmed

PROGRAM

DEFR

“ ”.