Lanair MXB360 User Manual
Page 8

2-1/2” Boiler
Supply Connection
CL
CL
CL
8“
2“
16.5”
16.5” min.
8”
8”
16.5”
33”
47.5”
CL
Dimension as per job specifications and local codes
Boiler Vent
Connections
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:30 pm CST
8
Section 2 - Typical Boiler Room Layout
Section 3 - Boiler Room Air Requirements
Figure 1
1. To ensure safe efficient operation, the boiler system must be supplied with sufficient air for combustion and ventila-
tion (see Fig. 2)
2. Unless properly controlled, avoid the use of forced ventilation, since it can create an undesirable pressure differen-
tial between the boiler room and air source.
3. All boilers located in confined rooms should have free access to ventilation and combustion air from two perma-
nent openings. One opening should terminate within 12" of the ceiling, the other within 12" from the floor
(see Fig. 2). Each opening shall have at least 1 sq. inch free area per 1,000 BTU/HR of burner input. Openings should
freely connect with areas having adequate infiltration of outside air
WARNING: Failure to provide an adequate supply of fresh air for combustion will result
in hazardous operating conditions. Do not use an exhaust fan in the boiler room.
!