E ex d iic t6, Cenelec / iec, Health and safety at work act – Fire Fighting Enterprises Talentum UV/IR2 Flame Detector User Manual

Page 4: Installation, Enclosure with front cover removed

background image

4

CENELEC / IEC





E Ex d IIC T6





















Table 2 Type of Protection Codes

Table 3 Temperature Classification



Table 4 Subdivisions of Group II Gases


Temperature

Class

Referred to

ambient of

-20°C to +40°C

Maximum

Surface

Temperature

T6 85°C

T5 100°C

T4 135°C

T3 200°C

T2 300°C

T1 450°C

Detectors approved to T6.

Code

Type of
Protection Code

Equipment

Category

ia Intrinsic

safety

1

ib Intrinsic

safety

2

d

Flameproof 2

These Flame Detectors are approved ‘d’.

Gas Group

Representative Gas

Other Gases, Liquids, Vapours

IIC

Hydrogen

Acetylene, Carbon Disulphide

IIB

Ethylene

Diethyl ether, Tetrafluoroethylene

IIA

Methane

Butane, Methanol, Petroleum, Propane, Styrene

These Flame Detectors are approved IIC for listed gases in EN 50014.

Conformity with
European Standards.
IEC marking omits
this character

Explosion Protection
symbol

9

FLAME SENSOR

ELECTRONIC MODULE.

1

2

3

4

5

6

7

8

FLAME SENSOR

CONNECTION TERMINALS.

JCE EExd HOUSING EMH29

WITH FRONT REMOVED.

Health and Safety at Work Act


In the UK all equipment must be installed and disposed of (as required) within the legislative
requirements of the Health & Safety at Work Act 1974.

Installation




No modification should be made to the enclosure without reference to the manufacturer as
unauthorised modification to an approved enclosure will invalidate the certificate/approval.

1.

The enclosures are supplied with drilled and tapped entries. See enclosure drawing

2.

The surface of the machined/threaded flamepaths between cover and body must be

protected from scratches or damage during installation. Any such damage can destroy
the validity of the enclosure.

3.

Before the cover is refitted, the flamepath/threaded joint between cover and body must
be thoroughly wiped clean of dirt, grit or other foreign substances, and then a thin
coating of an approved form of non-setting grease applied to joint/threads. Ensure the
gasket o-ring is free from damage.


4.

Threaded covers must be screwed on to a minimum of 5 full threads of engagement and
then locked in position with the locking screw provided.

5.

All tapped entries must be fitted with an approved flameproof (EExd) device which is
equivalent or superior to the gas group of the enclosure.

6.

The enclosure should be mounted using the two rear M6 tapped holes.

7.

Do not scratch the glass.

8.

Glanding of cables should be as in Selection of Cable Gland section.

Enclosure with Front Cover Removed