0 meter technical specifications (continued) – E-Mon E34-6003200R*KIT User Manual
Page 8

CLASS 3400 METER
62-0391-01
8
3.0 METER TECHNICAL SPECIFICATIONS
(CONTINUED)
Input Voltage
Configuration
3-wire (Delta) Or 4-wire (Wye)
Mains Voltage Input Up To 600 VAC RMS Available
Input Power
6 VA Maximum Rating
Current Sensor
Rating
Up To 3200 Amps RMS AC Available
Power Factor
0.5 Leading Or Lagging
Line Frequency
50-60 Hz
Metering Accuracy
ANSI C12.20
Voltage Operating
Range
+/-10% Of Rated Load
Temperature Range -20 C To +50 C (Standard indoor enclosure):
Relative Humidity
Range
0-95% Non-condensing
Altitude
2000 Meters Maximum
Voltage Overload
+25% Continuously: +100% For 20 Cycles
Current Sensor
Overload
100% For 1 Minute Without Damaging Meter
Pollution Degree
Degree 2 In Accordance With IEC 664
Installation
(Overvoltage)
Category
Category III
Measurement
Category
Category III
Enclosure Material
UL Type 1 or Type 4X
Display Readout
4-line LCD
Standard Ranges
4-Wire Wye 208 VAC: 100, 200, 400, 800,1600 Amp
3-Wire Delta240 VAC: 100, 200,400,800,1600 Amp
4-Wire Wye 480 VAC: 100, 200, 400, 800,1600 Amp
3-Wire Delta480 VAC: 100, 200,400,800,1600 Amp
4-Wire Wye 600 VAC: 100, 200, 400, 800,1600 Amp
Modem Interface
Cable:
UL-listed/rated telephone
cord, 4-conductor, 300 VAC,
stranded conductors 22-26
AWG.
Cable Connector:
RJ-11 IDC termination
Ckt Input Isolation
5.3K VAC
Baud Rate:
9600
- E34-6001600R*KIT E34-600800-R*KIT E34-600400-R*KIT E34-600200-R*KIT E34-600100-R*KIT E34-4803200R*KIT E34-4801600R*KIT E34-480800-R*KIT E34-480400-R*KIT E534-480200-R*KIT E34-480100-R*KIT E34-4003200R*KIT E34-4001600R*KIT E34-400800-R*KIT E34-400400-R*KIT E34-400200-R*KIT E34-400100-R*KIT E34-2083200R*KIT E34-2081600R*KIT E34-208800-R*KIT E34-208400-R*KIT E34-208200-R*KIT E34-208100-R*KIT