Fulton Heating Solutions, Inc.
972 Centerville Road, Pulaski, NY 13142
Call: (315) 298-5121 • Fax: (315) 298-6390
www.fulton.com
invictus-bro-2012-1206
The heat transfer innovators.
A and AR Model
Right Side View
A and AR Model
Front View
27
3
/
8
” (*)
10
1
/
2
”
38
1
/
2
” (*)
48
1
/
2
”
50
1
/
2
”
50
3
/
4
”
60
7
/
8
”
5
7
/
8
”
33
1
/
2
”
4”
33"
E
W and WLB Model
Left Side View
W and WLB Model
Front View
37
13
/
16
”
33
1
/
2
”
50
3
/
4
”
51
9
/
16
”
25
3
/
4
”
10
1
/
2
”
SPECIFICATIONS
AND DIMENSIONS
specifications:
EnERgy sOuRcE
aIR sOuRcE
WaTER / gROunD sOuRcE
mODEl
IVs-095-a IVs-095-aR
IVs-095-W IVs-095-Wlb
Dimensions:
Width IN
33.5 33.5 33.5 33.5
Length
IN 48.5
48.5
25.75
25.75
Height IN
50.75 50.75 50.75 50.75
Application
Heating Only
Heat / Cool Reversible
Heat / Cool Simultaneous Heat / Cool Simultaneous
Environmental Component
Outdoor Air
Outdoor Air
Water (Lake / Pond)
Ground
Input
BTU/Hr
95,500 95,500 95,500 95,500
Max Output Heat
BTU/Hr
139,200
134,800
142,600
133,800
Max
Efficiency
%
146 141 149 140
Max Output Cool BTU/Hr (Tons)
N/A
64,800 (5.4)
59,400 (4.9)
58,400 (4.9)
Max
Hot
Water
Temp
°F
140 140 149 140
Min Cold Water Temp
°F
37
37
37
37
Max Ambient Op. Temp
°F
113
113
113
113
Min Ambient Op. Temp
°F
-20
-20
10
10
Electrical
Rating
V/Ph/Hz
208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
Electrical Consumption
kW
0.75
0.75
0.4
0.4