Air source models, Applications, Performance – Fulton Invictus (IVS) Heat Pump Systems User Manual
Page 4: Thermal efficiency vs. outdoor air temperature

ELECTRIC
CHILLER
(Off)
HEAT PUMP
BOILER
HEAT
LOAD
O
utside W
all
OUTDOORS
INDOORS
SYSTEM
PUMP
ELECTRIC
CHILLER
COOLING
LOAD
O
utside W
all
OUTDOORS
INDOORS
(Off)
HEAT PUMP
BOILER
SYSTEM
PUMP
AIR SOURCE MODELS
APPLICATIONS:
The air source models of the gas
absorption heat pump can be used
for hydronic heating and cooling
applications. The IVS-095-A model is
for heating only, and the IVS-095-AR
is heating/cooling reversible.
Hydronic Cooling Capacities:
(IVS-095-AR Model)
Hydronic Heating Efficiencies:
(IVS-095-A Model)
PERFORMANCE:
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
-5
-10 -15 -20
150
145
140
135
130
125
120
115
110
105
100
95
90
85
Ambient Temperature (°F)
Th
er
m
al
E
ffic
ie
nc
y,
P
er
ce
nt
Heating
Setpoint:
86°F
113°F
122°F
140°F
Thermal Efficiency vs. Outdoor Air Temperature
Outdoor Temp.
(°f)
Output (bTu/hr, Tons)
37.4°f setpoint
Output (bTu/hr, Tons)
44.6°f setpoint
Output (bTu/hr, Tons)
50.0°f setpoint
59
64,800
5.40
63,800
5.32
64,800
5.4
66
63,500
5.29
63,500
5.29
64,100
5.34
77
60,100
5.01
62,400
5.20
63,300
5.28
86
54,300
4.53
60,700
5.06
61,800
5.15
95
44,000
3.67
57,700
4.81
59,400
4.95
104
.....
.....
51,200
4.27
54,600
4.55
113
.....
.....
.....
.....
46,100
3.84
Graphic: Air source models are installed