Liquid level control llc4 series single probe – Mody Pumps MS 252 User Manual

Page 8

background image

332

LLC41A01 06.04.02

Liquid Level Control
LLC4 Series
Single Probe

Single Probe Level Control for Conductive Liquids
Adjustable or Fixed Sensing up to 250K

Fill or Drain Operation Available
24, 120, or 230 V AC Models are Available
Isolated AC Voltage on the Probes
4 A Resistive SPDT Isolated Contacts

Description

The LLC4 combines resistance sensing circuitry with
solid state timing to provide single probe level
maintenance. On adjustable units, the sensitivity
adjustment allows accurate level sensing while ignoring
foaming agents and floating debris. Transformer
isolated 12 V AC is provided at the probe to prevent
electrolysis. A trickle current of less than 1 mA
determines the presence or absence of liquid between
the probe and common. The LLC4 Series can be
used with many types of low voltage (resistance
changing) transducers to perform other control
functions like temperature limit control, photo limit
control, condensation sensing, and ice sensing.

Operation

Drain (Pump Down Mode): When the liquid level
rises and touches the probe, a fixed time delay begins.
This time delay prevents rapid cycling of the output
relay and its load. At the end of the time delay, the
output relay energizes and remains energized until
the liquid level falls below the probe. The output relay
then de-energizes and remains de-energized until the
liquid again touches the probe.

Ordering Table

Control

Type

ON/OFF (Single Level) Resistance sensor

with built-in time delay to prevent rapid cycling

Sense Voltage

12 V AC at probe terminals

Sense Resistance

Factory fixed or adjustable to 250K

Sense Resistance Tolerance

Adjustable - guaranteed range

Factory fixed +/-10%

Input

Voltage

24, 120, or 230 V AC

Tolerance

24 V AC

-15% ... +20%

120 & 230 V AC

-20% ... +10%

Frequency

50 ... 60 Hz

Output

Type

Electromechanical relay

Form

Isolated single pole double throw (SPDT) contacts

Rating

4 A resistive at 240 V AC; 1/10 hp at 240 V AC

Protection

Surge

IEEE C62.41-1991 Level A

Isolation Voltage

1500 V RMS between input, output, & probe

Mechanical

Mounting

Plug-in socket

Termination

8-Pin plug-in

Package

2.91 x 2.39 x 1.78 in. (73.9 x 60.7 x 45.2 mm)

Environmental

Operating Temperature

-20°C ... +60°C

Storage Temperature

-40°C ... +80°C

Weight

6 oz (170 g)

Series

Input

Time Delay
(Seconds)

Sense
Resistance

Example P/N:

LLC44A1A

Fixed –

LLC46B5F50

Operation

Specify fixed
resistance
(

1

...

250

)

in 1K

increments

–Specify fixed delay
(

1

...

60

) secs. in

1 s increments

P = Probe C = Probe Common V = Voltage

Relay contacts are isolated. Dashed lines are
internal connections.

Connect common to conductive tank. Additional
probe is necessary for non-conductive or
insulated tanks.

Approvals:

Level probe
P/N: LLP-24

Accessories

Panel mount kit
P/N: BZ1

Octal
8-pin socket
P/N: NDS- 8

Electrode
P/N: WCC-1138

Electrode with
common connection
P/N: WCC-1138-3

Hold down clips
P/N: PSC8

Inches (Millimeters)

Fill (Pump Up Mode): When the liquid level falls
below the probe, a fixed time delay begins. This time
delay prevents rapid cycling of the output relay and
its load. At the end of the time delay, the output relay
energizes and remains energized until the liquid level
rises and touches the probe. The output relay then
de-energizes and remains de-energized until the liquid
level again falls below the probe.

2

- 24 V AC

4

- 120 V AC

6

- 230 V AC

X

LLC4

A

- Drain

B

- Fill

X

A

- Adjustable

X

X

F

- Fixed

Technical Data

See accessory page at the end of this section.

Sales Information 1-800-431-2308 Technical Assistance 1-800-377-SSAC (7722) www.ssac.com