beautypg.com

Micromod MOD: Modcell 2050R 2051FZ2, Foxboro 62H to 2050R Conversion Accessory User Manual

Page 2

background image

92902-92

2051F Conversion Instructions for Foxboro 62H


4. In the "Milliamp Input **Menu**", configure the analog input for an electrical input of 10 to 50

milliamps. In the "Milliamp Output **Menu**", configure the control output current to 10 to 50
milliamps.


5. Configure other options and features in the instrument as required for the application.

6. Remove power from the instrument.


PANEL INSTALLATION

Caution!!


Be sure all power has been disconnected at the source before attempting terminations.

1. For quickest change-out, preconfigure the MODCELL 2051 controller prior to panel installation.

Configuration data resides in a nonvolatile memory location.


2. Remove the 62H instrument from its shelf position. Disconnect the instrument cable from the back of

the instrument.


3. Cut off the 62H instrument connector from its cable. Strip back the outer insulation jacket of the

cable three to four inches.


4. Make power and field connections per I/O instructions as outlined in IB-23C650-_._

5. Apply instrument power. Tune the instrument as required for the loop.










2