INPUTS
NOTE: Refer to pages 2-9 and 2-36 before you begin wiring.
Figure 2-39 Analog Input 2: Voltage Input
Figure 2-38 Analog Input 1: Voltage Input
5
6
7
8
JA
±12V Input
-
Common
+
+
-
2
3
4
8
JA
±12V Input
-
Common
+
+
-
Analog Input 1:
Voltage Input Wiring
(JA, Pins 2, 4, 8)
The Analog Input 1 can be used with either ±12 VDC or
0-20 mA inputs. Figure 2-38 displays the ±12 VDC
option.
For the differential inputs:
Connect JA pin 2 to the positive differential signal
source.
Connect JA pin 4 to the negative differential signal
source.
Connect JA pin 8 to the common of the differential
signal source.
For the non-differential inputs:
Connect JA pin 2 to the signal voltage source.
Connect JA pin 4 and JA pin 8 to the common of the
signal source.
Analog Input 2:
Voltage Input Wiring
(JA, Pins 5, 7, 8)
The Analog Input 2 can be used with either ±12 VDC or
0-20 mA inputs. Figure 2-39 displays the ±12 VDC
option.
For the differential inputs:
Connect JA pin 5 to the positive differential signal
source.
Connect JA pin 7 to the negative differential signal
source.
Connect JA pin 8 to the common of the differential
signal source.
For the non-differential inputs:
Connect JA pin 5 to the signal voltage source.
Connect JA pin 7 and JA pin 8 to the common of the
signal source