Jog forward, Jog reverse – CONTREX CX-1200 User Manual
Page 19
![background image](/manuals/334429/19/background.png)
Page 17
Run
(J6 pins 5, 3)
Digital Input 3
When the Run input (J6, pin 6) is momentarily shorted
to common, the CX-1200 enters the Run state. As a
momentary input, Run is internally latched and does
not need to be maintained closed by an operator
device.
NOTE: Close the R-Stop, H-Stop, and F-Stop inputs
prior to entering the Run state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the CX-
1200 will not enter run.
Jog Forward
(J6 pins 6, 8)
Digital Input 4
Jog Forward is a maintained input. When it is closed,
it sends a forward speed command signal to the drive
at the selected Jog Setpoint. As a maintained input,
Jog Forward is only active when the operator device is
closed.
NOTE: Close the R-Stop, H-Stop and F-Stop inputs
prior to entering the Jog state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX-1200 will not enter Jog.
Jog Reverse
(J6 pins 7, 8)
Digital Input 5
Jog Reverse is a maintained input. When it is closed,
it sends a reverse speed command signal to the drive
at the selected Jog Setpoint. As a maintained input,
Jog Reverse is only active when the operator device is
closed.
NOTE: Close the R-Stop, H-Stop and F-Stop inputs
prior to entering the Jog state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX-1200 will not enter Jog.
Figure 18 Run
RUN
3
5
J6
Com
DI_3
Figure 19 Jog Forward
JOG FORWARD
6
8
J6
DI_4
Com
Figure 20 Jog Reverse
JOG REVERSE
7
8
J6
DI_5
Com