2.12.1 P
OWER
W
IRING DIAGRAM
The 0.38 A fuse in the +24VDC power lead is required for protection of the amplifier in the event of amplifier or
power supply malfunction.
8
7
3
6
5
4
2
1
1
2
6
3
4
5
7
8
24 Vdc
SUPPLY
POWER
+
24 V
0 V
FUSE
Figure 6 - Wiring diagram for use with 24 VDC power supply
The power source for the power supply shall be fused at the proper rating to prevent over current in
the supply leads due to a power supply failure.
2.12.2 O
UTPUT WIRING
The load in this connection may be an indicator, recorder, data acquisition device or the analog input terminals of a
control device such as a DC drive or a programmable logic controller. The output signal at this terminal is
undamped and is the output terminal that provides that fastest response to changes in the transducer (load-cell) load.
Note that the cable’s shield drain wire should be connected at only one end, preferably at the “receiving end”.
1
8
5
6
7
2
4
3
1
7
5
6
3
2
4
8
+ / - 10V LOAD
5000 OHM MIN
RESISTANCE
+
SHIELD GND
Figure 7 - Output Wiring, +/- 10V Analog