Error message, Event log, Classified errors and classified status – Hach-Lange SC 200 Modbus Module User Manual User Manual
Page 10
Error message
Displayed Error
Definition
Resolution
FLASH FAILURE
The external serial flash
memory Read/Write fails
Contact technical service
Event Log
Refer to
for diagnostic device information.
Table 3 Event log
Event
Description
0: Power Up Event
Logs the power up time
1: Device Comm Loss
Reports the loss of communications
with a device. (Data: Device Index)
2: Device Comm Restore
Reports the restored communications
with a device (Data: Device Index)
3: Software Restart Event
Reports a software restart.
Classified errors and classified status
show the classified error
register and the classified status 1-4 register flags for main
measurements. All the sensors and analyzers supply this signal quality
information at the same register address.
Table 4 Classified errors – register 49930
Bit
Error
Note
0
Measurement Calibration
Error
An error has occurred during the last
calibration.
1
Electronic Adjustment Error
An error has occurred during the last
electronic calibration.
2
Cleaning Error
The last cleaning cycle failed.
Table 4 Classified errors – register 49930 (continued)
Bit
Error
Note
3
Measuring Module Error
A failure has been detected in the
Measuring Module.
4
System Re-initialization
Error
Some settings have been detected
inconsistent and set to factory defaults.
5
Hardware Error
Any hardware error in general has been
detected.
6
Internal Communication
Error
A communication failure within the device
has been detected.
7
Humidity Error
Excessive humidity has been detected in
this device.
8
Temperature Error
Temperature within the device exceeds
specified limit.
9
Reserved for future use
Fixed at 0
10
Sample Warning
Some action is required with the sample
system.
11
Questionable Calibration
Warning
The last calibration was of questionable
accuracy.
12
Questionable Measurement
Warning
One or more of the measurements of the
device are of questionable accuracy
(Quality bad or out of range).
13
Safety Warning
A condition has been detected which may
result in a safety hazard.
14
Reagent Warning
Some action is required with the reagent
system.
15
Maintenance Required
Warning
Maintenance is required on this device.
10 English