Master Programming Mode

CAUTION: Before entering Master Programming, please contact your local professional water dealer.

5. Tank in Service (Display Code TS)

Press the Extra Cycle button. Use this display to set whether tank one or tank two is in service. This option setting

is identified by “TS” in the upper left hand corner of the screen. This parameter is only available if the number of

tanks has been set to 2. There are two possible settings:

Tank One in Service: U1
Tank Two in Service: U2

6. Unit Capacity (Display Code C)

Press the Extra Cycle button. Use this display to set the Unit Capacity. This setting specifies the treatment

capacity of the system media. Enter the capacity of the media bed in grains of hardness when configuring a

softener system, and in the desired volume capacity when configuring a filter system. This option setting is

identified by “C” in the upper left hand corner of the screen. The Unit Capacity parameter is only available if the

control type has been set to one of the metered options. Use the Up and Down buttons to adjust the value as

needed.

7. Feedwater Hardness (Display Code H)

Press the Extra Cycle button. Use this display to set the Feedwater Hardness. Enter the feedwater hardness in

grains per unit volume for softener systems, or 1 for filter systems. This option setting is identified by “H” in the

upper left hand corner of the screen. The feedwater hardness parameter is only available if the control type has

been set to one of the metered options. Use the Up and Down buttons to adjust the value as needed.