English – Burkert Type TAT002 User Manual
Page 14

12 - 0911
english
NOTE
You can access hidden parameters by holding down the
keys SET + for 3 sec in the programming level HY. The
message Pr2 appears.
Digital inputs
HES
Temperature increase/
Set-value is increased/lowered by HES
Reduction
during an energy-saving phase
Activation via digital input
(i1F = Es).
i1F
Function of the digital
EAL = external alarm; OFF = unused;
Input
bAL = serious external alarm;
Es = Energy saving mode Start/Stop;
onF = switch the device ON/OFF
externally;
C-H = reverse the control effect
i1P
Polarity of the digital
CL: active with closed contact
input
OP: active with opened contact
did
Alarm delay time
For i1F = EAL or i1F = bAL.
of the digital input
The corresponding alarm then takes
(0...120 min)
place display or message.
Miscellaneous
Adr
Serial address RS485
Address for XJ500 recording
(1...247)
system. Identifies the device if it
is linked into a ModBUS-compatible
system.
OnF
Set device to STAND-BY
no = not possible via keyboard
yes = STAND-BY can be activated by
holding down the SET button
for
at least 4 sec. If you want to change the
set-value, hold down the SET button for
approx. 2 sec.
Ptb
Number of the parameter-
only read-out value
table
rEL
Version
only read-out value
Pr2
Display of the parameters
display only
in Level Pr2