Step Six

Step Seven

INSTALLATION

INSTALLATION

Mounting the LU30 properly is critical to operation. If the LU30 is
installed such that it is recessed in a fitting or flange, follow the crite-
ria listed below. For an I.D. less than 3", do not recess the LU30 more
than 1" for best results.

Factory Settings:

The LU30 sensor is preset at the factory. When powering up the sen-
sor the first time, the factory settings will be active. If at any time in
you need to return to these settings, remove power from the sensor
and wait 10 seconds. Press the [Set] and [Menu] buttons simultane-
ously while powering up the sensor.

Changing Display Units:

The LU30 comes preset to measure in inches. To change the unit to
display centimeters, remove power to the unit and wait 10 seconds.
Press [

s] and [Set] simultaneously while powering up the sensor. The

LU30 will now read in centimeters. To return to inches, remove
power and wait 10 seconds. Press [

t] and [Set] simultaneously while

powering up the sensor.

Depth

Radius

Radius

(Feet)

(Inches)

(cm)

1'

1.2"

3.1 cm

2'

2.1"

5.2 cm

3'

2.9"

7.3 cm

4'

3.7"

9.5 cm

5'

4.6"

11.6 cm

6'

5.4"

13.7 cm

7'

6.2"

15.9 cm

8'

7.1"

18.0 cm

9'

7.9"

20.1 cm

10'

8.8"

22.3 cm

11'

9.6"

24.4 cm

12'

10.4"

26.5 cm

13'

11.3"

28.7 cm

14'

12.1"

30.8 cm

15'

13.0"

32.9 cm

16'

13.8"

35.1 cm

17'

14.6"

37.2 cm

18'

15.5"

39.3 cm

19'

16.3"

41.3 cm

20'

17.2"

43.6 cm

21'

18.0"

45.7 cm

22'

18.8"

47.8 cm

23'

19.7"

50.0 cm

24'

20.5"

52.1 cm

25'

21.4"

54.2 cm

Maximum Application Range

The maximum range of Echotouch™ is 24.5 feet at 110 dB. Yet a
number of factors can reduce the overall quality of signal return and
shorten the accurate range of the transmitter. To determine the maxi-
mum application range of the product, follow the signal return for-
mula against the echo attenuation graph below.

ALIGN READING (dB)

10

20

30

40

50

50

100

150

200

250

300

00

DISTANCE FROM FACE OF TRANSDUCER (inches)

IDEAL

CUR

VE

10 dB

ABSORPTION

2

3

1

4

20 dB

ABSORPTION

EXAMPLE:
¥ OPTIMIZE ALIGNMENT

1: Distance from transducer = 50"
2: Highest possible ALIN = 35 dB

(under ideal conditions)
Adjust mechanical alignment of unit
to maximize displayed ALIN value

¥ PREDICT MAXIMUM RANGE
USING ALIGN VALUE

3: If the actual ALIN = 15dB at D = 50"
4: Maximum Tange = 170"

Depth

Inner

Diameter

Radius

Depth

VACUUM

Flange I.D.

(Inches)

3
4
5
6
7
8

3
7

11
15
19
26

Flange I.D.

(Inches)

Avoid

Interference
from side of

tank

Do not install

LU30 at

an angle

Avoid Inter-

ference from

obstructions

in tank

LU30 will not

operate in

vacuum

LEVL

EC 4

EC20

RLAY

HSET

LSET

INCHES (cm)

288" (731.2 cm)

8" (20.3 cm)

N/A

5" (12.6 cm)

288" (731.2 cm)

SAF1/2

F/S

ALIN

OFF/ON

TANK

value

SAF1

FAST

N/A

OFF

N/A

288" (731.2 cm)

Warning

Always install the 2” Viton gasket with the LU30-50__. The G
threaded version of the Echotouch will not seal unless the gasket
is installed properly.

When installing the LU30, never tighten the transmitter from the
body. Always use the wrench flat located above the threads.