beautypg.com

Specifications, Technology, Sinking vs. sourcing – Flowline LU30 EchoTouch User Manual

Page 2: 2" npt (2" g) 2.8, Lu30 - 5 0

background image

Step One

SPECIFICATIONS

Range:

0.5 to 24.5 feet (15 cm to 7.4 m)

Accuracy:

± 0.25% of span (air)

Resolution:

0.125” (3 mm)

Frequency:

50 kHz

Pulse rate:

8 pulses per second

Beam width:

8° conical

Blocking distance:

0.5' (15 cm) minimum

Display type:

4 segment LED

Display units:

Inch (cm)

Memory:

Non-volatile

Supply voltage:

14-36 VDC

Consumption:

200 mA

Current flow:

Source / sink

Signal output:

4-20 mA, three-wire

Signal invert:

4-20 mA / 20-4 mA

Signal averaging:

Fast / slow

Calibration:

Push button

Relay type:

(1) SPDT

Relay output:

250 VAC, 10A, 1/4 hp

Relay mode:

Selectable, NO or NC

Relay indication:

ON / OFF status

Contact resistance:

30 milliohm

Fail-safe diagnostics: Relay reverts to safe position
Process temp.:

F: -4º to 140º C: -20º to 60º

Temp. compensation: Automatic over entire range
Electronics temp.:

F: -40º to 140º C: -40º to 60º

Pressure rating:

30 psi (2 bar) @ 25 °C., derated @ 1.667 psi
(.113 bar) per °C. above 25 °C.

Enclosure rating:

NEMA 4X (IP65)

Enclosure material:

Polypropylene, U.L. 94VO

Transducer material: Polyvinylidene Fluoride
Cable jacket mat’l:

Vinyl

Cable length:

9” (22 cm)

Mounting threads:

2” NPT (2" G)

Mounting gasket:

Viton (metric only)

Conduit connection: Single, 1/2" NPT
Classification:

General purpose

CE compliance:

EN 61326 EMC
EN 61010-1 Safety

Technology

An ultrasonic sound wave is pulsed eight times per second from the base of the transducer. The
sound wave reflects against the process medium below and returns to the transducer. The micro-
processor based electronics measure the time of flight between the sound generation and
receipt, and translates this figure into the distance between the transmitter and process medium
below.

Sinking vs. Sourcing

The LU30 is manufactured in two different outputs, sourcing and sinking. A sourcing transmitter
uses the negative of the power supply as the reference for the entire system. When using a sourc-
ing unit, make sure the negative of the ground is the common for the entire system. A sinking
transmitter uses the positive of the power supply as the reference for the entire system. When
using a sinking unit, make sure the positive of the ground is the common for the entire system.

Holding down the
[MENU] key will
scroll the display in
the following
sequence.

4.9"

(124 mm)

1.3"

(32 mm)

3.6"

(92 mm)

2" NPT (2" G)

2.8"

(71 mm)

LU30 - 5 0

_

_

Mounting Thread

0 - 2" NPT
6 - 2" G

Switch Output

3 - 4-20 mA, Sourcing
4 - 4-20 mA, Sinking

Ultrasonic Transmitter

+ -

DC Power

Supply

14-36 VDC

- +

Red

Black

White

(+)

(-)

(S)

+ -

DC Power

Supply

14-36 VDC

- +

Red

Black

White

(+)

(-)

(S)

40

35

30

25

20

15

10

05

00

-40

-20

00

20

40

60

80

Acceptable

Range

Unacceptable

Range

Temperature/Pressure Derating

Operating Pressure (psi)

Temperature ( C)

100

80

60

40

20

0

Maximum Temperature/Voltage

Derating @ Continuous 20 mA

Ambient Sensor

T

emperature ( C)

Operating Voltage (VDC)

Acceptable

Range

Unacceptable

Range

12

16

20

24

28

32

36

2,000

1,500

1,000

500

0

Acceptable

Range

Unacceptable

Range

Flowline Electrical Loading Limits

Max. Series Resistance (Ohms)

12

18

24

30

36

Supply Voltage (VDC)

LU30-50_4, LU50-70_4
LU30-50_3, LU50-70_3

MENU

SET

RELAY

Echotouch

TM

Ultrasonic Transmitter

LE

V

E

L

,

E

C

4

,

E

C

2

0

,

R

LA

Y ,

HS

ET,

LS

ET

,S

AF

1/

2,

FA

S

T

/S

L

O

W

,

A

L

IN

,

O

F

F/

ON

, TA

NK, (value)

9" Cable

(22 cm)

Red

Black

White

Blue

Green

Yellow

(+)

(-)

Signal

COM

NC

NO

Sourcing

LU30-50_3

Sinking