Flowline LU29 EchoSonic II User Manual
Page 6

6
Enter the appropriate tank level set points for your application.
Units. Display measurements in inches
or centimeters.
Sensor Height. Distance measured from
the bottom of the empty tank to the
bottom of the transducer. Under factory
configuration, this becomes the 4 mA set
point.
Fill Height. Distance measured from the
bottom of the empty tank to the
maximum fill height within the tank.
Under
factory
configuration,
this
becomes the 20 mA set point.
Tank Level Settings
The options on the right of the WebCal™ screen to finalize the
configuration.
Write to Unit. Send your configuration into EchoSonic® II.
Wiring Diagram. Open PDF wiring schematic of your
configuration.
Advanced. Configure advanced settings. Read the section
below on advanced setting options
Factory Config. Return EchoSonic® II to the original factory
configuration.
Clear Screen. Clears the screen of configuration settings.
Config File. Name, save, open or print your configuration for
later use.
Finalize Settings