5 measured values and adjustment parameters, Measured value tc - collector temperature, Measured value ts - dhw sensor temperature – DE DIETRICH BSC...E - BSP...E - BESC...E User Manual
Page 16: Measured value kwh - amount of heat, Measured value tc - self-calibration time
16
BSC...E - BSP...E - BESC...E
11/05/12 - 300027781-001-01
4.5 Measured values and adjustment parameters
*with S3 sensor only (optional)
*
The regulator has a safety system that cuts off the tank at
temperatures of over 80°C.
Measured value TC - Collector temperature
The value TC shows the temperature in °C given by the collector
sensor in real time.
Measured value TS - DHW sensor temperature
The value TS shows the temperature in °C given by the tank sensor
in real time
Measured value kWh - Amount of heat
The value kWh shows in kWh the total amount of heat produced by
the installation since the regulator was put into service.
The quantity of heat (kWh value) can only be used for checks
carried out for personal reasons.
Measured value tc - Self-calibration time
The value tc shows the self-calibration phase time remaining in
seconds. During the self-calibration phase, the pump operates at full
speed (100 %); its speed is only controlled after the self-calibration
phase.
Channel
Abbreviation
Range
Increment
Factory setting
Collector temperature
TC
[-50.0 ... 250.0] °C
-
-
Calorifier temperature
TS
[-50.0 ... 250.0] °C
-
-
Amount of heat
kWh
[0 ... 9999] kWh
-
-
Pump regime
PC
[0 ... 100] %
-
-
Self-calibration time
tc
[0 ... 5] minutes
-
-
Reference temperature difference
DT
[10 ... 20] K
0.1
20
Set temperature of the solar calorifier
SX
[20 ... 80] °C
0.1
60
Maximum collector temperature
CX
[100 ... 125] °C
0.1
100 °C
Self-calibration phase
tu
[1 ... 5] minutes
1
1
Pump minimum speed
PN
[50 ... 100] %
5
50
Tubular solar collector function
FT
[0 ... 1]
1
0
Maximum flow rate
Fx
[0 … 20] l/min
0.1
6.7
Manual mode
MM
[0 ... 2]
1
2
Measured values
Adjustment parameter