4.5 Measured values and adjustment parameters

*with S3 sensor only (optional)

*

The regulator has a safety system that cuts off the tank at
temperatures of over 80°C.

„

Measured value TC - Collector temperature

The value TC shows the temperature in °C given by the collector
sensor in real time.

„

Measured value TS - DHW sensor temperature

The value TS shows the temperature in °C given by the tank sensor
in real time

„

Measured value kWh - Amount of heat

The value kWh shows in kWh the total amount of heat produced by
the installation since the regulator was put into service.

The quantity of heat (kWh value) can only be used for checks
carried out for personal reasons.

„

Measured value tc - Self-calibration time

The value tc shows the self-calibration phase time remaining in
seconds. During the self-calibration phase, the pump operates at full
speed (100 %); its speed is only controlled after the self-calibration
phase.

Channel

Abbreviation

Range

Increment

Factory setting

Collector temperature

TC

[-50.0 ... 250.0] °C

-

-

Calorifier temperature

TS

[-50.0 ... 250.0] °C

-

-

Amount of heat

kWh

[0 ... 9999] kWh

-

-

Pump regime

PC

[0 ... 100] %

-

-

Self-calibration time

tc

[0 ... 5] minutes

-

-

Reference temperature difference

DT

[10 ... 20] K

0.1

20

Set temperature of the solar calorifier

SX

[20 ... 80] °C

0.1

60

Maximum collector temperature

CX

[100 ... 125] °C

0.1

100 °C

Self-calibration phase

tu

[1 ... 5] minutes

1

1

Pump minimum speed

PN

[50 ... 100] %

5

50

Tubular solar collector function

FT

[0 ... 1]

1

0

Maximum flow rate

Fx

[0 … 20] l/min

0.1

6.7

Manual mode

MM

[0 ... 2]

1

2

Measured values