6 troubleshooting, 1 breakdown codes, 1 safety alarms – DE DIETRICH ECODENS DTG 1300-24 ECO _ V-130 User Manual
Page 12: 2 sensor alarms, 3 before contacting the installer, Troubleshooting, Safety alarms, Sensor alarms, Before contacting the installer

12
DTG 1300-24 Eco / V130
11/09/09 - 300010111-001-B
6. Troubleshooting
6 Troubleshooting
In the event of a fault, the display indicates an alarm message by
alternately showing AL and a code from which the type of fault can
be determined.
6.1 Breakdown codes
6.1.1
Safety alarms
6.1.2
Sensor alarms
6.1.3
Before contacting the installer
`
Try to restart the boiler once by pressing the key Q on the
control panel.
`
If this fails after a second try to restart,inform the professional
responsible for maintaining the boiler.
`
Note the following information on the appliance's rating plate:
- Boiler type
- Date of manufacture
- Serial no. of the appliance
- Type of gas used.
Alarm code
Meaning
cA
Igniter fault
cI
Ionization error
tS
Overheating alarm
PA
No water
cd
Communication error with the safety control box (card side)
c8
Internal error safety control box
A1
Communication error with the safety control box (box side)
TH
Communication with the communicating remote interrupted
Alarm code
Meaning
40
Fault external sensor
41
No outside sensor on start-up if outlet sensor B present
42
Fault outlet sensor B
50 or 51
Fault temperature sensor heating outlet
54 or 44
Domestic hot water outlet sensor fault
58 or 59
Fault electronic manometer
C002672-B