EBARA Submersible Sump/Drainage Pumps

EPD / Optima

Required

Minimum

Pump Capacity

Basin Diameter

up to 35 GPM

18"

over 35 GPM

24"

over 60 GPM

30"

over 100 GPM

36"

over 150 GPM

48"

General Application Information

(cont.)

Safety Information and Introduction

Before handling this pump, always disconnect
the power first.

This pump should only be serviced by a qualified person or a factory
trained person.

Basin and Cover
The basin should not be less than 18 inches in diameter and 24 inches deep.
Larger diameters are advisable in instances of increased pump capacity requirements:

The basin should be located such that all water flows into the basin due to gravity.
Outdoor installations should be at a sufficient depth to ensure protection from freezing.

Note: Optima-3SS1 and EPD-3SS1 slimline automatic can operate in a 12'' diameter
basin or 8'' x 8'' square basin.

Maintenance Tips

Every three or four months:

1) Clean the pump screen or inlet opening. If your sump collects the discharge
from an automatic washing machine, cleaning will be required more often. (Before
removing the pump be sure to disconnect the unit from electrical power; and
reconnect after completion of cleaning);

2) Pour enough water into the sump to cycle the pump and assure its proper

functioning.

Annually:

Remove and clean the pump. Clean the sump pit also.

WARNING

!

CAUTION

This instruction manual includes necessary items for installation, operation and maintenance.
Read this manual carefully to ensure correct installation, operation and maintenance.

Be sure to keep this instruction manual on hand for future reference.

!