Refrigerant piping cont – AAON CL-230 User Manual
Page 28

28
REFRIGERANT PIPING cont.
TABLE RP-3 Predetermined Line sizes for Single Circuit CL units with R-410A
Tons System
R-410A
Connection Size
Predetermined Line Size
Suction Line Liquid Line Hot Gas Bypass Reheat Suction Line Liquid Line Hot Gas Bypass Reheat
45
1
1-1/8 in.
5/8 in.
7/8 in.
7/8 in.
1-3/8 in.
5/8 in.
5/8 in.
3/4 in.
2
3
4
60
1
1-3/8 in.
5/8 in.
7/8 in.
7/8 in.
1-3/8 in.
3/4 in.
3/4 in.
7/8 in.
2
3
4
70
1 1-3/8
in.
5/8 in.
7/8 in.
7/8 in.
1-3/8 in.
3/4 in.
3/4 in.
7/8 in.
2
1-5/8 in.
1-5/8 in.
7/8 in.
1-1/8 in.
3
1-3/8 in.
1-3/8 in.
3/4 in.
7/8 in.
4
1-5/8 in.
1-5/8 in.
7/8 in.
1-1/8 in.
75
1
1-5/8 in.
5/8 in.
7/8 in.
7/8 in.
1-5/8 in.
7/8 in.
3/4 in.
1-1/8 in.
2
3
4
95
1
1-5/8 in.
5/8 in.
7/8 in.
7/8 in.
1-5/8 in.
7/8 in.
3/4 in.
1-1/8 in.
2
7/8 in.
1-1/8 in.
2-1/8 in.
1-1/8 in.
7/8 in.
3
5/8 in.
7/8 in.
1-5/8 in.
7/8 in.
3/4 in.
4
7/8 in.
1-1/8 in.
2-1/8 in.
1-1/8 in.
7/8 in.
TABLE RP-4 Predetermined Line sizes for Single Circuit CL units with R-22
Tons System
R-22
Connection Size
Predetermined Line Size
Suction Line Liquid Line Hot Gas Bypass Reheat Suction Line Liquid Line Hot Gas Bypass Reheat
45
1
1-3/8 in.
5/8 in.
7/8 in.
7/8 in.
1-5/8 in.
5/8 in.
3/4 in.
7/8 in.
2
3
4
60
1
1-3/8 in.
5/8 in.
7/8 in.
7/8 in.
1-5/8 in.
3/4 in.
7/8 in.
1-1/8 in.
2
3
4
70
1
1-3/8 in.
5/8 in.
7/8 in.
7/8 in.
1-5/8 in.
3/4 in.
7/8 in.
1-1/8 in.
2 2-1/8
in.
3 1-5/8
in.
4 2-1/8
in.
75
1
1-3/8 in.
5/8 in.
7/8 in.
7/8 in.
2-1/8 in.
3/4 in.
7/8 in.
1-1/8 in.
2
3
4
95
1
1-3/8 in.
5/8 in.
7/8 in.
7/8 in.
2-1/8 in.
3/4 in.
7/8 in.
1-1/8 in.
2
2-1/8 in.
7/8 in.
1-3/8 in.
1-1/8 in.
1-1/8 in.
1-3/8 in.
3
1-3/8 in.
5/8 in.
7/8 in.
3/4 in.
7/8 in.
1-1/8 in.
4
2-1/8 in.
7/8 in.
1-3/8 in.
1-1/8 in.
1-1/8 in.
1-3/8 in.