Table 8b – Amana PGC(24-60)B User Manual

Page 28

background image

28

Outdoor

Indoor

PGC42

PGC48

PGC60 and PGB58

Air Temp.

at

Air

Temp.

Indoor

Air Temp.

Pressure @ Unit

Gauge Fittings

Amps

Indoor

Air Temp.

Pressure @ Unit

Gauge Fittings

Amps

Indoor

Air Temp.

Pressure @ Unit

Gauge Fittings

Amps

Condenser

Inlet

(Dry Bulb)

at Evap.

Inlet

(Wet Bulb)

Difference

Between

Coil Inlet

and Outlet

Low

Side

High

Side

Total to

Unit

Difference

Between

Coil Inlet

and Outlet

Low

Side

High

Side

Total to

Unit

Difference

Between

Coil Inlet

and Outlet

Low

Side

High

Side

Total to

Unit

A

B

C

D

E

B

C

D

E

B

C

D

E

° F.

° F.

° F.

PSIG

PSIG

Amps

° F.

PSIG

PSIG

Amps

° F.

PSIG

PSIG

Amps

77

7

86

332

23.1

8

88

327

23.8

9

83

343

34.9

115

72

12

85

331

23.1

13

88

327

23.8

15

83

342

34.8

67

18

85

332

23.1

18

88

327

23.8

21

82

342

34.7

62

23

84

332

23.2

24

87

326

23.7

26

81

341

34.6

77

8

85

313

22.2

8

88

308

23.2

10

82

323

33.3

110

72

13

85

313

22.2

13

87

308

23.2

15

82

322

33.2

67

18

84

312

22.1

18

87

308

23.1

21

81

322

33.2

62

23

83

311

22.1

24

86

307

23.1

27

80

321

33.1

77

8

84

294

21.3

8

87

291

22.5

10

82

303

31.8

105

72

13

84

293

21.2

13

86

290

22.5

15

81

303

31.8

67

18

83

294

21.3

18

86

290

22.5

21

80

303

31.8

62

23

82

293

21.2

24

85

290

22.4

27

80

302

31.7

77

8

84

277

20.4

8

86

274

21.9

10

81

285

30.5

100

72

13

83

276

20.4

13

86

273

21.9

15

80

285

30.4

67

18

83

275

20.4

19

85

273

21.8

21

80

285

30.5

62

24

82

274

20.3

24

84

272

21.8

27

79

284

30.4

77

8

83

259

19.6

8

85

256

21.3

10

80

268

29.2

95

72

13

82

258

19.6

13

85

257

21.2

16

80

267

29.2

67

18

82

257

19.5

19

84

256

21.2

22

79

267

29.2

62

24

81

256

19.5

25

84

255

21.1

28

78

266

29.1

77

8

82

241

18.8

8

84

240

20.6

10

79

251

28.1

90

72

13

82

241

18.8

14

84

240

20.6

16

79

250

28.0

67

19

81

240

18.8

19

83

240

20.6

22

78

250

28.0

62

24

80

240

18.8

25

83

239

20.5

28

77

249

27.9

77

8

82

226

18.1

9

84

225

20.0

11

79

234

27.0

85

72

13

81

224

18.1

14

83

225

20.0

16

78

234

26.9

67

19

81

225

18.1

19

83

224

20.0

22

78

233

26.9

62

24

80

223

18.0

25

82

224

19.9

28

77

232

26.8

77

8

81

211

17.5

9

83

200

19.4

11

78

218

25.9

80

72

13

81

210

17.5

14

82

210

19.4

16

78

218

25.9

67

19

80

211

17.5

20

82

209

19.4

22

77

218

25.9

62

24

79

208

17.4

25

81

209

19.3

28

76

217

25.8

77

9

80

196

16.9

9

82

196

18.8

11

78

204

25.0

75

72

14

80

196

16.9

14

82

196

18.8

16

77

203

24.9

67

19

79

194

16.8

20

81

195

18.8

22

76

203

24.9

62

25

79

194

16.8

25

80

195

18.8

28

76

202

24.8

Table 8B

A Columns - All data based on indoor dry bulb of 80° F and rated air flow. As indoor dry bulb temperature increases, a slight increase will occur in indoor air temperature differential

between inlet and outlet. Low and high side pressures and power will not change.

B Columns - A properly operating unit should be within ±3° F of the typical (dry bulb) value shown.
C Columns - A properly operating unit should be within ±3 PSIG of the typical value shown.
D Columns - A properly operating unit should be within ±7 PSIG of the typical value shown.
E Columns - A properly operating unit should be within ±2 amps of the typical value shown.