Alpha Technologies XM2-300HP Wall-Mount Rack User Manual
Power
Power
1. The dimensions of the rack are 23.59" H x 15.15" W x 8.58" D
(600.0mm x 385.0mm x 218.0mm). Select a location that allows
sufficient clearance on the top, bottom and sides for cabling required
for the installation.
2. For center mounting, locate one stud and drill pilot hole. Install first
user-supplied 5/16" lag bolt and hang the shelf using keyslot. Mark
and drill second hole and install second lag bolt. Secure both lag
bolts once shelf is positioned.
3. For corner mounting inside of enclosures, use drawing to locate the
four corner holes. Use four user-supplied 5/16" bolts to mount rack.
4. To install an SPI, use either of the two SPI mounting holes on the
top of the rack. Place the SPI so that the seizure screw is facing up.
Tighten the SPI to 130 in-lbs of torque.
Installation Instructions
Wall-Mount Rack (WMR) for XM2-300HP and Battery
12.00" / 305.0mm
15.15" / 385.0mm
20.50"
521.0mm
1
1
#10-32 ground studs
Fig. 1, Mounting hole layout
Fig. 2, Ground wire stack up
1
For proper operation of the Power Supply and Communications
Module, external grounding of the rack is required.
IMPORTANT:
Installation Procedure:
Recommended Tools and Materials:
• Ratchet with 1/2" and 5/16" (or metric equivalent) sockets
• Level
• Two user-supplied 5/16" x 3" (or metric equivalent) lag bolts
• 1" Torque Wrench
• Stud finder (optional)
• Drill with 1/4" (or metric equivalent) drill bit
• Tape measure (optional)
Install the system in a sheltered, weather-protected location
inaccessible to the general public.
NOTE:
CAUTION!
5. The rack is connected to ground via either of the #10-32 ground
studs circled in Fig. 1. Follow the proper stack up as shown in Fig.
2 to attach the supplied lock washer, #10-32 nut and user-supplied
ground wire. Refer to applicable codes to determine additional
grounding requirements.
For Power Supply installation and connection, refer to the XM2-300HP Technical
manual (p/n 017-877-B1) at www.alpha.com
23.59"
600.0mm
The populated rack weighs approximately 120 lbs (54.3kg). The
installer must verify the wall is capable of supporting the loaded rack.
Direct mounting to a wall stud and use of customer-supplied 3/4"
plywood backing is required.