Customer connections, List 0,6 : 5 module with cxc controller, Can terminated – Alpha Technologies Cordex 48-1kW 19 6000W Installation User Manual
Page 44: Can unterminated
![background image](/manuals/317403/44/background.png)
SIZE
DWG NO.
TYPE
B
SHEET
TITLE
ISSUE
DATE
OF
TOLERANCES
SCALE
APPROVED
CHECKED
DRAWN
DESIGN
MATERIAL
FINISH
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.
ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF
REVISIONS
LTR
DESCRIPTION
APPD
DATE
REV
X.X
0.04"
X.XX
0.02"
X.XXX
0.01"
[X]
1mm
[X.X]
0.5mm
[X.XX]
0.25mm
030-706-08
CUSTOMER CONNECTION,
6 MOD OR 5 MOD w CXC SUP.
48-1kW CXRC 19/23" MNT SHELF
PER P.O. and
Doc. 070-024-83
1 3
DGW
DGW
2004/05
2004/05
D2
c 2004 ARGUS TECHNOLOGIES
O
C
DIMENSIONS ARE IN INCHES WITH METRIC [mm] IN BRACKETS: INCHES [mm]
J.K.
2004/05
W.E.S.
2004/05
NTS
REV BY
B SPECIFIED RECTIFIERS FED BY TB1 & TB2
M.P. 2005/11
C UPDATED AC I/P TERMINAL BLOCK
FROM LINE 2 TO L2/N
M.P. 2007/09
WES
TB1
L1
L2/N
#6-32 SCREWS
TYPICAL AC INPUT TERMNINAL BLOCK
( TB1 SHOWN )
TB1 FEEDS RECTIFIERS 1, 3, 5
TB2 FEEDS RECTIFIERS 2, 4
C
J3
P1
P1
J3
E2 - COMMON (+)
E1 - LIVE (-)
AC INPUT KNOCKOUT PLATE
(REVERSIBLE)
AC
INPUTS
1.125" KO
ACCEPTS 3/4" FITTING/CONDUIT
.875" KO
ACCEPTS 1/2" FITTING/CONDUIT
#1/4-20 CHASSIS GROUND
CXCM BACKPLANE
(707-340-20)
DC
OUTPUT
USES 1/4-20 x 5/8" OUTPUT LUGS
TIGHTEN TO 8 FT-LB
TB1
TB2
LIST 0,6 : 5 MODULE WITH CXC CONTROLLER
CAN TERMINATED
JUMPER SETTING FOR P1
1. GND
2. CAN H
3. NOT CONNECTED
4. CAN L
5. NOT CONNECTED
6. NOT CONNECTED
CAN OUT RJ12 OFFSET
PIN OUT (J3)
CAN UNTERMINATED