Basic unit, shelf, Mechanical, Connections – Alpha Technologies Cordex 48-1kW 19 6000W Installation User Manual
Page 35: Safety

Specifications for Apha’s Cordex 48-1kW 19" Shelf System
Apha Technologies Ltd.
030-706-B1 Rev A
Printed in Canada. © 2012 Apha Technologies Ltd. APHA and CORDEX are trademarks of Apha Technologies Ltd. All Rights Reserved.
Page 1 of 3
Basic Unit, Shelf
Output:
111A @ 54Vdc nominal (124.8A maximum @ 48V)
Recommended Feeder Breaker
Single Phase:
15A, #12AWG, 90 deg.C wire at 30 deg. C ambient (per rectifier)
[refer also to AC Feeder Protection/Sizing section of the manual]
Mechanical
Dimensions*:
177.3mm H x 444.5mm W x 303.4mm D (rectifier front panel 18.8mm D)
[6.98" H x 17.50" W x 11.95" D (rectifier front panel 0.74” D)]
Mounting*:
19” or 23” mid-mount, 23” flush
Weight:
7.5 kg (16.5 lb.)
Connections*
AC Input:
#6-32 screw terminal blocks
Chassis ground:
1/4-20 stud
Communications:
CAN (bus), in and out, RJ-12 offset; Ethernet RJ-45
DC Output:
1/4-20 x 5/8” studs
Signal wiring:
Terminal blocks
0.75 to 0.14mm
2
(#18 to #26 AWG)
Safety
CSA
C22.2 No. 60950-1
UL
60950-1
CE
EN 60950, CB Scheme
73/23/EEC Low Voltage Directive with amendment 93/68/EEC
EN 60950
Rectifier output shall be rated SELV suitable for connection to TNV-1 circuits
* See drawings at the rear of this manual.