Leds, Alarm conditions, Progress and status indication – Alpha Technologies CXPS 48-1.8-M2, 48V Pos Gnd User Manual
Page 20: Reset, Ethernet port, Analog input channels, Voltage inputs, Current inputs, Temperature inputs, Digital input channels

Argus Technologies Ltd.
053-991-C0 Rev A WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 6 of 28
2.3.2 LEDs
The CXC has three LEDs located on the front panel. These are used to display the alarm status of the power
system, CXC progress and status during startup, and file transfers.
2.3.2.1 Alarm
Conditions
The CXC illuminates the LED that corresponds to the system alarm status. The following show
the corresponding alarm status for each LED color:
Green – OK, no alarms present
Yellow – Minor alarm is present (no major alarms)
Red – Major alarm is present.
Only one LED is illuminated at a time during alarm conditions.
2.3.2.2
Progress and Status Indication
The LEDs are also used in the following situations:
Base unit validation – all three LEDs are on at the same time.
File transfer – when recovering from invalid firmware application – the red LED is illuminated.
2.3.3 Reset
A reset button is located on the front panel for restarting the CXC’s microprocessor.
NOTE: Refer also to the software manual – always select the Reset menu item before pressing the reset button.
2.3.4 Ethernet
Port
The Ethernet port is designed for CXC connection to a user supplied network (TCP/IP secured by user) via a front
panel RJ-45 jack (Figure 5) and a standard network cable.
Local access (e.g. laptop computer) is also possible from the Ethernet port connection using a standard network
crossover cable.
2.3.5
Analog Input Channels
The CXC has analog input channels for voltage, current, and temperature.
2.3.5.1 Voltage
Inputs
Two voltage input channels, V1 and V2, provide monitoring of discharge and charge voltage.
The CXC software is pre-configured to monitor V2 for system voltage; used as the system
reference for rectifier float voltage, low voltage disconnect (LVD), system high voltage alarm,
and system low voltage alarm. V1 is pre-configured (factory wired) to monitor battery voltage.
2.3.5.2 Current
Inputs
The CXC software is pre-configured to monitor I1 for load current using an external 50mV
current shunt.
2.3.5.3 Temperature
Inputs
Two temperature input channels, T1 and T2, provide monitoring of battery temperature and
temperature compensation (temp comp) or room/ambient temperature. A voltage is supplied to
these terminals to power the temperature sensors.
2.3.6 Digital
Input
Channels
The CXC has digital input channels to monitor alarm/control signals from rectifiers, converters and many other
types of equipment.