Hardware specifications, cxcm2, Recommended signal wire sizes (as per ul/csa) – Alpha Technologies CXPS 48-1.8-M2, 48V Pos Gnd User Manual
Page 10

Specifications for Argus’ CXCM2 Cordex Controller Modular 2RU Model Continued
Argus Technologies Ltd.
018-588-B1 Rev B WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 2 of 2
Hardware Specifications, CXCM2
CPU: Coldfire
RAM: 8MB
Flash:
4MB standard, 8MB optional
Display:
160 x 160 pixel grayscale LCD
Front Panel Controls:
Reset button and touch panel (display and input device)
LED’s:
System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)
Audio:
Built-in speaker for alarm and popup message tones
Dimensions:
86mm H x 128mm W x 255mm D
(3.4” H x 5.0” W x 10“ D)
Weight:
1.8 kg (3.9 lb.)
Mounting:
Integrated on Cordex 2RU series 19” and 23” shelves
Communication Ports:
Ethernet RJ-45, CAN [see shelf specifications]
Relay Outputs:
Six (6) Form C, 60Vdc 1A maximum
Digital Inputs:
Six (6), 0 to 60Vdc
Analog Inputs and System Signals, Argus #018-573-20-040:
Two (2) DC voltage, 0 to 60Vdc
One (1) current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source
Analog Inputs and System Signals, Argus #018-573-20-044:
Two (2) DC voltage, 0 to 60Vdc
Two (2) current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source
Four (4) bi-voltage, ±60Vdc
Recommended Signal Wire Sizes (as per UL/CSA)
Wire Size Range*:
0.14 to 0.75mm
2
(#26 to #18 AWG)
via DB connectors or terminal block kit (see list options)
Temperature Range:
0 to 50°C
(32 to 122°F)
CAUTION – TO REDUCE RISK OF FIRE, USE ONLY 0.14mm
2
(#26 AWG) OR LARGER WIRE.
* See drawings at the rear of this manual.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information. Specifications are subject to change without notice.