2 rcu voltage configuration, 3operation, Procedure – Alpha Technologies CFR Redundant Control Unit User Manual
Page 15
13
3
Operation
3.2
RCU Voltage Configuration
Figure 3.6
Input 1 and 2 Pin Jumpers on the Power Board
Input 1 Pin Jumpers
Input 2 Pin Jumpers
R 10
120 V
120 V
R 9
R 8
R 1
R 2
R 3
R 4
R 5
R 6
R 7
208 V
or
240 V
208 V
or
240 V
R 11
R 12
F 2
F 1
1
1
2
2
3
3
4
4
5
5
J 1
J 2
12
3
4567
8
J 3
NOTE: The Input 1 and 2 voltages must be configured identically.
DANGER: This procedure should be done only by qualified personnel.
DANGER: Verify the power is OFF before opening the front panel.
The RCU is designed so it is voltage configurable for 120/208/240 VAC.
PROCEDURE:
Switch the Input 1 and 2 circuit breakers OFF.
Remove the two Phillips screws on the sides of the front panel.
Carefully lower the panel 45 degrees.
Locate the Input 1 and 2 pin jumpers on the power board.
1
2
4
3
See also other documents in the category Alpha Technologies Equipment:
- AlphaCell GelCell Series (32 pages)
- FXM 650, 1100, 2000 UPS (96 pages)
- Cordex 48-1.2kW (68 pages)
- Radium MiniBay (57 pages)
- Fiber Backhaul Enclosure (FBE) (19 pages)
- FBE2322 Enclosure System (38 pages)
- FlexNet PMR, GMR Series (49 pages)
- Te25xh (38 pages)
- FlexNet MPS48-12M - Technical Manual (33 pages)
- FlexNet MPS48-12M - Quick Start Guide (2 pages)
- FlexNet ELPM 300-48D (25 pages)
- FlexNet FMPS (40 pages)
- FlexPoint AX Series (34 pages)
- FlexPoint FPR1207-F - Technical Manual (18 pages)
- FlexPoint FPR1207-F - Quick Start Guide (2 pages)
- AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual (79 pages)
- AlphaGen CE-3x2 5K-T 48Vdc (95 pages)
- AlphaGen PN-6x-T 7.5kW 48Vdc (95 pages)
- AlphaGen 3.5_5.0kW Kohler COM5 (80 pages)
- Security Bar Field For UPE-3, UPE-6, UPE-M3, UPE-M6, PN Series and CE Series (2 pages)
- AMPS80 HP (116 pages)
- 255A Bypass Switch (24 pages)
- AMP24 HP (108 pages)
- FXM350_Micro350 UPS (112 pages)
- CFR 600, CFR 600XT, CFR 1000 (70 pages)
- BPS Series Bypass Switch (36 pages)
- CFR Intelligent Interface Device (54 pages)
- CFR 5000, CFR 5000RM (88 pages)
- CFR 3000, CFR 3000RM (86 pages)
- CFR 1500, CFR 1500RM (83 pages)
- CFR 1500, CFR 2000, CFR 2500, CFR 3000 (76 pages)
- Continuity: 1000_2000_3000 (48 pages)
- Continuity Battery Pack (20 pages)
- Continuity: 6K_10K (52 pages)
- Micro, Micro XL, Micro XL3 UPS (99 pages)
- Micro Secure UPS (80 pages)
- Te17 (32 pages)
- Te45 (68 pages)
- Te41, 48V (76 pages)
- Te41, 24V (72 pages)
- Te43 (60 pages)
- AlphaGuard AG-CMT Installation (2 pages)
- AlphaGuard AG-CMT-3SC_4SC-P (2 pages)
- Digital Midtron DM-3200 AT (2 pages)