Operation

3.2

RCU Voltage Configuration

Figure 3.6

Input 1 and 2 Pin Jumpers on the Power Board

Input 1 Pin Jumpers

Input 2 Pin Jumpers

R 10

120 V

120 V

R 9
R 8

R 1

R 2

R 3

R 4
R 5
R 6

R 7

208 V

or

240 V

208 V

or

240 V

R 11
R 12

F 2

F 1

1

1

2

2

3

3

4

4

5

5

J 1

J 2

12

3

4567

8

J 3

NOTE: The Input 1 and 2 voltages must be configured identically.

DANGER: This procedure should be done only by qualified personnel.

DANGER: Verify the power is OFF before opening the front panel.

The RCU is designed so it is voltage configurable for 120/208/240 VAC.

PROCEDURE:

Switch the Input 1 and 2 circuit breakers OFF.

Remove the two Phillips screws on the sides of the front panel.

Carefully lower the panel 45 degrees.

Locate the Input 1 and 2 pin jumpers on the power board.

1

2

4

3