Gorman-Rupp Pumps S8B1-E100 460/3 1432260 and up User Manual
Page 44
S SERIES PUMPS
OM-06259
MAINTENANCE AND REPAIR
PAGE E - 18
diate (48) so that the lower bearing (31) seats
squarely in the intermediate bearing bore.
Secure the gasket (14) to the cap with a light coat
ing of gasket adhesive.
Position the intermediate over the bearing and
align the mounting holes with those in the bearing
cap. Apply `Never‐Seez' or equivalent compound
to the threads of the capscrews (12). Install the
capscrews and lockwashers (13); torque the caps
crews evenly in a cross‐sequence to 20 ft. lbs. (240
in. lbs. or 2,8 m. kg.).
Motor Housing And Intermediate Reassembly
(Figure E-1)
Use fresh solvent to clean the bores and all gasket
surfaces of the motor housing (18), completely re
moving any old gasket and cement material. In
spect the sealing surfaces for burrs, nicks and pits
which could cause a poor seal, and repair or re
place as required.
Most cleaning solvents are toxic and
flammable. Use them only in a well ven
tilated area; free from excessive heat,
sparks, and flame. Read and follow all
precautions printed on solvent contain
ers.
Apply `3M Gasket Adhesive No. 847' or equivalent
compound to the motor housing gaskets (15, 16
and 43). Position the gaskets on the motor hous
ing, making sure the gaskets are properly seated
and the adhesive holds them securely.
Install a three‐leg sling in the intermediate flange
holes and lower the assembled intermediate and
rotor assembly into the motor housing. Use cau
tion to guide the upper bearing into the motor
housing bearing bore. Tap the intermediate with a
soft‐faced mallet until it mates tightly with the motor
housing.
Apply `Never‐Seez' or equivalent compound on the
threads of the motor housing studs (44). Secure
the intermediate to the motor housing with the
hardware (45 and 46); torque the nuts evenly in a
cross sequence to 120 ft. lbs. (1440 in. lbs. or 16,6
m. kg.).
Refer to PUMP END REASSEMBLY, and reas
semble the pump end components.
Terminal Housing And Power Cable
Reassembly And Installation
(Figure E-2)
The electrical power used to operate
this pump is high enough to cause inju
ry or death. Make certain that the control
handle on the control box is in the OFF
position and locked out, or that the pow
er supply to the control box has been
otherwise cut off and locked out, before
attempting to open or service the pump
assembly. Tag electrical circuits to pre
vent accidental startup. Obtain the ser
vices of a qualified electrician, and refer
to the wiring diagram(s) in INSTALLA
TION, Section B, to make electrical con
nections.
Clean the exterior of the power cable with warm
water and mild detergent. Check for obvious physi
cal damage. Check the cable for continuity and in
sulation resistance (see Electrical Testing in
TROUBLESHOOTING). Do not attempt repairs
except to cut off either end of the cable; splicing is
not recommended. Reinstall any wire tags or ter
minals which may have been removed.
Never attempt to alter the length or re
pair any power cable with a splice. The
pump motor and cable must be com
pletely waterproof. Injury or death may
result from alterations.
(Figure E-2)
Use oil to lightly lubricate the outside of the pump
power cable (13), and the bores of the terminal
housing (16), terminal gland (12) and gland bush
ing (8) for ease of assembly. Slide the terminal
gland, gland bushing and terminal housing onto
the cable, allowing approximately 3 ft. (1 m) of ca
ble to extend beyond the terminal housing. Tempo
rarily tape the green and yellow ground wires to the
cable.