7.8. Measuring tank with piping and valve shall be mounted on tank lid.
Measuring tank shall include a calibrated level indicator to allow
accurate measurement of concentrated chemicals for dilution.
7.9. Injection point assemblies shall be provided for each discharge.
Provide a (PVC/Kynar/316SS/C-20) injection quill with isolation valve
for each injection point (corporation stop shall be provided with each
quill).
(Note to Specification Writer: Corporation stop is used on low
pressure systems, typically cooling water systems, to allow removal
or reinsertion of the injection quill without draining the system.
Corporation stops are not used on systems above 150 psi.)
8.0
CONTROLS
Chemical Feed Systems shall be provided with all necessary controls
including motor starters and appropriately sized overloads such that
connection to a single (1PH-120/208v or 3PH-460/other) power supply is the
only required field electrical work. A motor starter with ON/OFF switch shall be
provided for each motor on the chemical feed system. Running lights shall be
provided for each motor. All switches, lights and other electrical components
shall be NEMA4. All electrical devices shall be wired in conduit to the control
panel.
(Note to Specification Writer: The following paragraph is required only for
systems using control signals for electric stroke length adjustment:
Signal wiring for milliamp or voltage follower signals shall
not be run in the same conduit and shall not be terminated
in the same enclosure box as power and motor control
wiring.)