beautypg.com

Resettable lockout, Water heater operation, Figure 23 sequence of operation – John Wood Power Vent (Non-ENERGY STAR qualified models) User Manual

Page 19

background image

rounding area for damage and call a qualified service tech-
nician to service the water heater and replace the flamma-
ble vapour sensor. If there is a problem with the wiring of the
flammable vapour sensor or the flammable vapour interface
the LED will flash the failure status code.

Resettable Lockout

The gas control/thermostat can be reset by unplugging the
power cord to remove power and then reinserting the plug
to restore the power. Robertshaw controls will automatically
attempt to reset after a 20 minute wait period. White-
Rodgers Intelli-Vent™ controls will automatically reset after
a 60 minute wait period. Also see "Troubleshooting Guide".

Water Heater Operation

Figure 23 shows the water heater's sequence of operation
when a call for heat is initiated. The ignition control module
will attempt to light the burner three times. If the ignition con-
trol does not detect ignition it will enter lockout mode and
flash the corresponding error code.

– 19 –

CONTROL CHECKS TO

ENSURE PRESSURE

SWITCH IS OPEN

BLOWER IS

ENERGIZED

CONTROL CHECKS TO

ENSURE PRESSURE

SWITCH CLOSES

INDICATING BLOWER

IS OPERATING AND

THERE ARE NO

VENTING BLOCKAGES

(INLET OR OUTLET)

IGNITER IS

ENERGIZED AND MAIN

VALVE IS OPENED

MAIN BURNER ON AND

THE FLAME IS

SENSED BY CONTROL

MAIN BURNER

CONTINUES TILL THE

WATER IN THE TANK

REACHES

THERMOSTAT

SETTING

MAIN BURNER SHUTS

OFF. BLOWER

CONTINUES FOR A
POST PURGE TIME

CALL FOR

HEAT

Figure 23 Sequence Of Operation

GAS CONTROL

SIDE VIEW

QUICK CONNECTS FOR

POWER SUPPLY AND IGNITER

LOCATED ON UNDERSIDE

OUTLET

PRESSURE

PORT

MANIFOLD PRESSURE

ADJUSTMENT (REMOVE

CAP FOR ACCESS)

3/4” NPT. WRAP

WITH TEFLON TAPE

(2 WRAPS MIN.)

GROUND

CONNECTION

GAS CONTROL

FRONT VIEW

GAS OUTLET

TO BURNER

GAS INLET

1/2” NPT

TEMPERATURE

ADJUSTMENT

BUTTONS

TEMPERATURE

INDICATORS

IGNITER AND FLAME

PROBE ASSEMBLY

FLAMMABLE

VAPOUR SENSOR

COMBUSTION

BLOWER

AIR

PRESSURE

SWITCH

HIGH
LIMIT

SWITCH

TO POWER SUPPLY

DISCONNECT AND

OVERLOAD

PROTECTION

WHITE

BLACK

CONNECTOR

GREEN

INTELLI-VENT

TM

CONTROL

BOTTOM VIEW

Figure 24 Gas Control/Thermostat Details and Wiring Diagram (White-Rodgers)

CONNECTOR

GREEN