beautypg.com

Appendix a appendix b – Bell & Gossett S14362C Glycol Make-up Unit User Manual

Page 6

background image

6

SYSTEM PIPING AND UNIT

INSTALLATION – FINAL CHECK LIST

____

1. Is the unit base properly leveled and secured?

____

2. Are all lubrication points properly lubricated?

____

3. Is the shut-off valve to the pump suction open?

____

4. Is the shutoff valve to the Diaphragm Expansion

Tank line open?

____

5. Are the shutoff valves for the make-up line open?

____

6. Is the Triple Duty Valve turned to suitable operating

position?

____

7. Is the piping properly supported to prevent strains

on unit?

____

8. Is the system, including the pumps, purged of debris

and air?

ELECTRICAL WIRING AND CONTROL

SETTINGS – FINAL CHECK LIST

____

1. Does the feeder line voltage correspond to the unit

voltage? Check the unit nameplate or motor terminal
connection.

____

2. Are the feeder wires correctly sized for the load?

____

3. Have all the power terminals in the control panel

been checked for tightness? This is imperative since
stranded wires tend to “flow” and become loose
after initial installation.

____

4. Are the pressure controls correctly set? The pres-

sure switch needs to be set for proper operation.
Any subsequent change in system operating condi-
tions may require resetting the controls. For best
results, use compressed air and a continuity meter
(across the switch) to reset the controls. The legend
plate on the control indicates approximate readings
only, therefore, should be used with caution.

WARNING: Electrical shock hazard. Inspect all elec-
trical connections prior to powering the unit. Wiring

connections must be made by a qualified electrician in
accordance with all applicable codes, ordinances, and
good practices. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.

WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the

ground lug provided in the enclosure to avoid potential
safety hazards. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL
INJURY, DEATH, AND/OR PROPERTY DAMAGE.

CAUTION: Seal damage may occur. Do not run
pumps dry. Fill and vent the pump volute prior to

operation. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN PROPERTY DAMAGE
AND/OR MODERATE PERSONAL INJURY.

Appendix A

Appendix B

WARNING: Electrical shock hazard. Single phase
or three phase AC power. Disconnect and lockout

power before servicing unit. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS PER-
SONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.