SYSTEM PREPARATION

Prior to pump start-up, closed heating and cooling systems

should be cleaned, drained, and refilled with clean water. The

system fluid pH must be maintained between 7 and 9.

START-UP

Do not start pump until the system has been filled and vented.

Air should be vented fr om the system by means of an air vent

located at a high point in the system. The system must be

completely vented prior to pump operation. Do not run NRF/

NBF/SSF circulators dry. Pump operation without water cir cu-

lation could result in pump and motor damage.

PERIODIC INSPECTION

Bell & Gossett NRF/NBF/SSF Cir culators are designed to

provide years of trouble free service. It is recommended that

periodic inspections be made to check for potential pr oblems

with the pump. If any leakage or evidence of leakage is pr

e-

sent, repair or replace the unit.

WARNING: HOT WATER LEAKAGE HAZARD

Pressurize the body slowly while checking for leaks at

all joints with gaskets or solder connections. Failur e to follow

these instructions could r esult in serious personal injury

and/or property damage.

WIRING INSTRUCTIONS

A. Loosen the scr ew securing the conduit box cover (wiring

compartment), and remove the screw & cover.

B. Attach the appropriate size connector to the hole in the side

of the conduit box.

C. Using a minimum size of 14 AWG copper electrical wire

(refer to your local code for wiring restrictions), wire the

motor to a single phase power sour ce that matches the

electrical rating on the pump nameplate. See Fig. 3. Use

the size of electrical wire as dictated by local code.

D. Connect the gr ound wire to the inside of the conduit box

with one of the gr een screws provided inside the box. See

Fig. 4.
NOTE: Electrical supply and gr ounding wires must be suit-

able for at least 90°C (194°F).
NOTE: Model NRF/NBF/SSF Cir culators are impedance

protected and do not require external overload protection.

WARNING: ELECTRICAL SHOCK HAZARD

Be certain that all connections ar e secure and the

conduit box cover is closed befor e electrical power is

connected. Failure to follow these instructions could r esult

in serious personal injury, death and/or property damage.

WARNING: ELECTRICAL SHOCK HAZARD

Disconnect and lock out the power befor e making

electrical connections. Failur e to follow these instructions

could result in serious personal injury or death.

S

PUMP

MOTOR

L

N

PUMP MOTOR
IMPEDANCE
PROTECTED

FUSIBLE DISCONNECT
OR CIRCUIT BREAKER BY
OTHERS

TYPICAL WIRING INSTALLATION SCHEMATIC

1Ø POWER SOURCE

TO REMOTE
CONTROL
IF REQUIRED

FIG. 3

FIG. 4

CONDUIT BOX WIRING DETAIL

ALTERNATE

GROUND SCREW

GREEN
GROUND
SCREW

LINE
LEADS

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700

Fax: (847) 965-8379

www.xyleminc.com/brands/bellgossett

Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.

FIG. 2

© 2013 Xylem Inc. P58671H January 2013

This manual is related to the following products: