Using a large screwdriver or an end wrench and a strap wrench on the impeller OD turn the

impeller counterclockwise to unscrew it from the motor shaft. The impeller is held in place with

Loctite and torque. Do not insert anything between the impeller vanes or motor fan blades as

damage may occur.

Grab the OD of the seal head assembly and remove. Remove the four capscrews that hold the

bracket to the motor and remove the bracket. Push the cup mounted seal seat out of the bracket

with a small screwdriver.

Clean the motor shaft and bracket recess with a clean lint free cloth.

Lubricate the OD of the cup mounted seal seat with soapy water or P80 Rubber Lubricant and push

into the bracket. Install the bracket onto the motor.

Check that the seal faces are clean, if not, gently wipe with a lint free cloth to prevent scratching.

The seal head assembly is a unitized design and should not be disassembled.

Lubricate the ID of the seal head assembly with soapy water or P80 and push onto the motor shaft.

Clean the motor and impeller threads. Apply Loctite 7471 Primer to the threads of the motor

and impeller. Allow to dry. Apply a small amount of Loctite Retaining Compound 609 or 680

to the threads.

Care must be used when applying Loctite so that it does not get on surrounding areas.

Screw the impeller onto the motor shaft. Using a large screwdriver or an end wrench and a strap

wrench on the impeller OD tighten the impeller to the motor shaft. Do not insert anything between

the impeller vanes or motor fan blades as damage may occur.

Torque the impeller to 20-25 ft-lbs. 25 ft-lbs can be approximated by turning the impeller until the

impeller hub is firmly against the motor shaft shoulder and then turning an additional 15 degrees.

Note: On three phase motors it is very important to follow these instructions. Failure to comply to

these instructions could allow the impeller to come loose during the motor rotation check if the

motor starts in reverse rotation.

Clean the bracket and volute gasket surfaces. Install a new gasket on the bracket.

Insert the motor assembly back into the pump casing. Tighten the casing capscrews evenly.

Close the drain value and open the isolation valves. Inspect pump for leaks. If not leaking,

return pump to service.