Product Description
General description i-ALERT
™
Condition Monitor
Description
The i-ALERT Condition Monitor is a compact, battery-operated monitoring device that
continuously measures the vibration and temperature of the pump power end. The
condition monitor uses blinking red LEDs to alert the pump operator when the pump
exceeds pre-set vibration and temperature limits. This allows the pump operator to make
changes to the process or the pump before a catastrophic failure occurs. The condition
monitor is also equipped with a single green LED to indicate when it is operational and has
sufficient battery life.
Alarm mode
The condition monitor enters alarm mode when either vibration or temperature limits are
exceeded over two consecutive readings within a ten minute period. Alarm mode is
indicated with two red flashing LEDs within two second intervals.
Temperature and vibration limits
Variable
Limit
Temperature
195°F (91°C)
Vibration
100% increase over the baseline level
Battery life
The i-ALERT Condition Monitor battery is not replaceable. You must replace the entire unit
once the battery runs out of power.
The battery life is not covered as part of the standard pump warranty.
This table shows the average condition monitor battery life under normal and alarm-mode
operating conditions.
Condition monitor operational state
Battery life
Normal operating and environmental conditions
Three to five years
Alarm mode
One year
Product Description
i-ALERT
™
Condition Monitor Installation, Operation, and Maintenance Manual