beautypg.com

Manual – Xylem Expert 3400 User Manual

Page 9

background image

Manual

Manual Expert 1400/3400 GB 0704

MJK Automation A/S
Byageren 7
DK-2850 Naerum
Denmark
Tel.: +45 45 56 06 56
Fax: +45 45 56 06 46
[email protected]
www.mjk.com

Safety Instructions

for electrical apparatus for explosion-hazadous areas

Designation according to Directive 94/9/EC

- Equipment group II
- Equipment Category: sensor and housing category 2
- For explosive mixtures of air and combustible gases vapour or mists

Area of application:
For explosive mixtures of air and combustible gases, vapour or mists:

Equipment category

Explosive gas-air mixtures (G)

Category 1

Zone 0, 1 or 2

Category 2

Zone 1 or 2

Category 3

Zone 2

Designation of explosion protection:

EEx ia IIC T6

- Electrical apparatus with explosion
- Protection to European standard
- Type of protection
- Apparatus group
- Temperature class

Marking of Expert transmitter type 1400/3400 for Ex environment

II 2 G EEx Ia IIC T6 means:

II: Equipment group:

Surface industry

2: Category:

Category 2 (Zone 1 and 2)

G: Explosive atmosphere:

Gas

E: European Standards.
Ex: Equipment for explosive atmospheres.
Ia: Ex Protection principle:

Intrinsically safety.

IIC: Gas groups:

Acetylene & hydrogen.

T6: Temperature class:

85°C surface temperature

2G

II

0539