1-2 Introduction

H-4161

1.1 Description

The H-4161 includes a microprocessor, LCD display, 16-bit digital-to-analog converter, precision voltage

reference and a 4-20mA current transmitter. The SDI-12 and 4-20mA sections are isolated from each

other with a high voltage digital opto-coupler. Data collected from the SDI-12 bus is scaled by the

microprocessor into a 16-bit value and loaded into the digital-to-analog converter. The digital-to-analog

converter directly controls the current transmitter.

The H-4161 has two SDI-12 ports. The primary SDI-12 port provides data monitoring and

communication with the H-4161 device itself. When programmed to initiate measurements, the H-4161

makes measurements and collects the data from a sensor connected to the auxiliary SDI-12 port.

1.2 Display

The H-4161 has a 2-line x 16-character Liquid Crystal Display (LCD) which shows the current

measurement data. Line-1 displays the most recently captured SDI-12 data parameter. If the sensor

buffer is invalid (no data captured or the previous measurement failed) the message “no data” is shown

instead of a number. Line-2 displays the current setting of the 4-20mA output. Note: the mA value is the

desired loop current setting which the microprocessor loads into the digital to analog converter. If the 4-

20 mA loop is open, or insufficient loop voltage is present the actual loop current may be zero or may not

match the value on the display.

SDI = xxx.xx ft -
Iout = xx.xx mA

The character on the right hand side of Line-1 is an activity “spinner”. Every time a measurement is

captured or initiated, the spinner changes (rotates). This indicator shows measurements are being made

even if the measurement data is static (not changing).

1.3 Connectors

The H-4161 has a 5-position connector for making +12V and SDI-12 connections. The primary SDI-12

terminal is connected to the data logger and it’s attached sensors. If the H-4161 is to initiate

measurements, the auxSDI-12 terminal is connected to the SDI-12 sensor to be monitored. The 2-

position connector is for making connections to the 4-20mA loop.