3-2 SDI-12 Command and Response Protocol

H-4161

3.1 Command Summary

The H-4161 supports the following SDI-12 commands:

Standard Commands:

aM! Make measurement

aM1! Make special measurement

aD0! Send Data

aV!

Verify

aI!

Send Identification

a!

Send Acknowledge

aAn! Change Address

Extended Commands:

aXTEST!

Displays the current module settings

aXHELP!

Displays the supported commands

aXRMM!

Read Module Mode (0=Monitor, 1=Initiate)

aXWMMn! Write Module Mode (0=Monitor, 1=Initiate)

aXRMA!

Read Monitored Address (0-9, A-Z, a-z)

aXWMAn! Write Monitored Address (0-9, A-Z, a-z)

aXRMP!

Read Monitored Parameter (1 to 9)

aXWMPn!

Write Monitored Parameter (1 to 9)

aXRAC!

Read AutoScan command setting (0 to 9)

aXWACn!

Write AutoScan command setting (0 to 9)

aXRMR!

Read Measure Rate (seconds)

aXWMRdd! Write Measure Rate (seconds)

aXSTM!

Set Transparent Mode

aXRIH!

Read High (max) data value for 20.0mA

aXWIHdd! Write High (max) data value for 20.0mA

aXRIL!

Read Low (min) data value for 4.0mA

aXWILdd! Write Low (min) data value for 4.0mA

aXSCSdd!

Set Current Stage (for testing 4-20mA)

aXSMdd!

Set Milliamp output (for testing 4-20mA)

Factory use only:

aXSDACdd! Set the DAC to dd counts (for testing 4-20mA)

aXSCL!

Set Calibration Low (DAC=500)

aXSCH!

Set Calibration High (DAC=65000)

aXRCL!

Read DAC Calibration Low

aXWCLdd! Write DAC Calibration Low

aXRCH!

Read DAC Calibration High

aXWCHdd! Write DAC Calibration High