Aquavar solo user interface board, Service factor amps – all motors – Xylem IMS SOLOQ 1 Aquavar SOLO Quick Installation Guide User Manual
Page 2

1AS Controllers
3AS Controllers
Pressure Ranges for All Available Transducers
Transducer
1AS15 / 3AS20
3AS30
3AS50
(Min. PSI)
(Max. PSI)
(Min. PSI)
(Max. PSI)
(Min. PSI)
(Max. PSI)
100 PSI
(1)
20
85
20
85
10
50
200 PSI
(2)
40
170
40
170
20
100
300 PSI
60
255
60
255
30
150
(1) Standard on 1AS15, 3AS20 and 3AS30
(2) Standard on 3AS50
Service Factor Amps – All Motors
Drive
Settings /
Protection
Pressure
Adjustment
Pressure
Transducer
Connection
Current Limit Dial
(Motor Overload Protection)
Switch Input
(Over
Pressure Protection,
Level Control)
TRANSDUCER
JUMPER
230 Volt
200 Volt
HP
1Ø 2-Wire
1Ø 3-Wire
3Ш
3Ш
CentriPro
1
Franklin Grundfos CentriPro
1
Franklin Grundfos CentriPro Franklin Grundfos CentriPro Franklin
½
4.7/4.7
6
6
6.3/6.1
6
6
N/A
N/A
N/A
N/A
N/A
¾
6.4/6.2
8
8.4
8.3/7.8
8
8.4
3.9
3.8
N/A
4.5
4.4
1
9.1/8.1
9.8
9.8
9.7/9.4
9.8
9.8
4.7
4.7
N/A
5.5
5.4
1½ 11.0/10.4 13.1
2
13.1
2
11.1/10.9 11.5
11.6
6.1
5.9
7.3
7.2
6.8
2
N/A
N/A
N/A
12.2
13.2
2
13.2
2
7.6
8.1
8.7
8.8
9.3
3
N/A
N/A
N/A
N/A
N/A
N/A
10.1
10.9
12.2
12
12.5
5
N/A
N/A
N/A
N/A
N/A
N/A
17.5
17.8
19.8
2
20.2
2
20.5
2
1. CentriPro 2-Wire motors have Generation 1 and Generation 2 amp ratings, see motor nameplate or motor data sticker that was supplied with motor.
2. Amps are higher than controller overload range - use of these motors will current limit and provide reduced performance.
Xylem Inc.
www.xyleminc.com
© 2012 Xylem Inc. IMS-SOLOQ-1 January 2012