Xylem IMS SOLOQ 1 Aquavar SOLO Quick Installation Guide User Manual
Aquavar solo – quick installation guide

Aquavar SOLO – Quick Installation Guide
1. Mount Aquavar SOLO Drive (in a vertical position);
• Must have 6” minimum clearance on all sides for proper cooling.
2. Wire Input Power to SOLO Drive (Single Phase, 230V)
• Review Circuit Breaker Sizing - see IMS-SOLOQ-2 or IM229
3. Wire Motor Drop Cable to SOLO Drive (75˚C Copper Wire min.)
• 3AS Models - Use with Three Phase, 230V, ¾ to 5 HP Motors
• 1AS15 Model - Compatible w/Single Phase, 230V Motors
❍
3-Wire - .5 - 2 HP CP / Pentek XE; .5 – 1.5 HP FE & Grundfos
❍
2-Wire - .5 – 1.5 CentriPro, Pentek XE, Franklin Elec. & Grundfos 2-Wire
– units with R05K or newer software only.
• Review Wire Sizing (Table 4 of IM229)
4. Mount Transducer and Confirm Transducer Cable Wiring
• Transducer cable maximum length = 200 feet
• Connect Pressure Transducer to piping manifold and to ground
5. User Interface Board Adjustments
• Select proper “Current Limit Setting” (equal to motor SFA)
• 1AS15 Only - Set “Pump Stop Sensitivity” - High is Default
• 3AS_ _ Only - Select maximum frequency setting (60 Hz or 80 Hz);
❍
60 Hz = matching Liquid End HP and Motor HP
❍
80 Hz = “over-speed” application; motor HP > Liquid End HP
• Dry Well Sensitivity - Set on “High” position;
❍
If nuisance tripping occurs, switch to “Low” position
• Low Pressure Cut-Off and Pressure Drop setting adjusted to application /
system requirements.
• Optional use of Secondary Switch Connection, refer to IM229
6. Adjust Tank Pressure
• Set approximately 20 PSI below pressure set point
• Adjust as needed to optimize - see IMS-SOLOQ-2 or IM229
7. Turn Drive Power On - Adjust Pressure - Purge Air
• Purge air from system and check for leaks
• Factory default is 50 psi - push and hold Increase Pressure button if
higher pressure is desired and also adjust tank pre-charge.
8. Check Motor Rotation and Confirm Performance
Refer to Aquavar SOLO Installation Manual, IM229, for complete details.
Check Motor Insulation Resistance on retrofit jobs before replacing drive.