Viii. troubleshooting of submersible motors – Xylem IM180 R3 Standard and Dual Voltage Motors User Manual
Page 14

12
CentriPro Motors Installation, Operation and Maintenance Manual
VIII. Troubleshooting of Submersible
Motors
1. Motor does not start but does not blow fuses or relay.
• No Power Supply → Replace fuses, breakers or check for loose or corroded connections and
motor lead terminals.
• Defective Connections → Correct connections.
2. Fuses or relay blow when motor starts.
• Incorrect Voltage → Apply correct voltage.
Voltage must be ±10% of rated (Nameplate).
• Incorrect Fuses or Relay → Replace with proper fuses and relay.
• Defective Capacitors → Replace with proper capacitors.
• Wrong Connections → Correct wrong connections or short circuit.
• Locked Rotor Conditions → Correct pump or well conditions.
• Insulation Resistance Down → Check the line and correct.
3. Motor runs for a while and then blows fuses or relay.
• Low Voltage or High Voltage → Apply rated voltage.
• Defective Capacitors → Replace with proper capacitors.
• Different Control Box for the Motor → Replace with proper control box.
• Defective Starting Voltage Relay → Replace with proper relay.
• Pump is Sand Clogged → Pull pump and clean well.
• Overheated Protector → Shield the control box from heat source.
The following conditions are stated to provide the owner with a list of criteria for maximum
motor life and to assure motor warranty.
Troubleshooting of Submersible Motors