Bell & Gossett S11865A TECHNOLOGIC 1100 SERIES PUMP CONTROLLER User Manual

Page 3

background image

Menu

Default

Allowable

Item # System Setup Display

Value

Range

Field Value

29)

Invert P.I.D.

No

Y/N

Used to change from direct to reverse

acting. P.I.D.

30)

Low Suct. Pr. Tmr

0

0-999

Low suction alarm proof time delay

in seconds. A value of 0 will disable

the option.

31)

High Suct. Pr. Tmr

0

0-999

High suction alarm proof time delay

in seconds. A value of 0 will disable

the option.

32)

High Sys. Press.

0

0-30,000

Value when high system pressure

alarm will be activated.

33)

HSP Proof Tmr

0

0-60

Proof time prior to

High System pressure shutdown.

34)

NFSD Test Pr. Tmr

0

0-999

No flow shutdown proof time delay,

seconds. A value of 0 will disable

the option.

35)

Min Speed Pr. Tmr

30

0-999

Length of time (seconds) drive(s) will operate

at min. speed during no flow shutdown

sequence. If = 0 drive(s) will not stop.

36)

Restart PV Drop

0

0-150

Max. difference between setpoint and

process variable prior to restart after no flow

shutdown. If = 0 no flow shutdown is disabled.

37)

Min. Run Timer

10

0-999

Time period (minutes) to ignore no flow

shutdown sequence after restart from no

flow shutdown.

38)

Active A-V Alarm

0

0-3

If = 0 Disabled

If = 1 Low Suction Alarm only

If = 2 High System Alarm only

If = 3 Low Suct. & High System Alarm

3

2.3.4 Press the CLEAR key to return to the User Setup

Menu.

2.3.5 Confirm the user setup values per the table on

page 4. Use the UP or DOWN ARROW keys to

move through the menu. To change values press

ENTER, modify the value using the numeric key

pad or UP and DOWN ARROW keys, press

ENTER to accept the modification.