Bell & Gossett S11865A TECHNOLOGIC 1100 SERIES PUMP CONTROLLER User Manual
Page 3

Menu
Default
Allowable
Item # System Setup Display
Value
Range
Field Value
29)
Invert P.I.D.
No
Y/N
Used to change from direct to reverse
acting. P.I.D.
30)
Low Suct. Pr. Tmr
0
0-999
Low suction alarm proof time delay
in seconds. A value of 0 will disable
the option.
31)
High Suct. Pr. Tmr
0
0-999
High suction alarm proof time delay
in seconds. A value of 0 will disable
the option.
32)
High Sys. Press.
0
0-30,000
Value when high system pressure
alarm will be activated.
33)
HSP Proof Tmr
0
0-60
Proof time prior to
High System pressure shutdown.
34)
NFSD Test Pr. Tmr
0
0-999
No flow shutdown proof time delay,
seconds. A value of 0 will disable
the option.
35)
Min Speed Pr. Tmr
30
0-999
Length of time (seconds) drive(s) will operate
at min. speed during no flow shutdown
sequence. If = 0 drive(s) will not stop.
36)
Restart PV Drop
0
0-150
Max. difference between setpoint and
process variable prior to restart after no flow
shutdown. If = 0 no flow shutdown is disabled.
37)
Min. Run Timer
10
0-999
Time period (minutes) to ignore no flow
shutdown sequence after restart from no
flow shutdown.
38)
Active A-V Alarm
0
0-3
If = 0 Disabled
If = 1 Low Suction Alarm only
If = 2 High System Alarm only
If = 3 Low Suct. & High System Alarm
3
2.3.4 Press the CLEAR key to return to the User Setup
Menu.
2.3.5 Confirm the user setup values per the table on
page 4. Use the UP or DOWN ARROW keys to
move through the menu. To change values press
ENTER, modify the value using the numeric key
pad or UP and DOWN ARROW keys, press
ENTER to accept the modification.