9. Bypass Range Set Menu
A. To protect the load, the function
of bypass auto-transfer is
activated only when the AC main
voltage is within the range of LO
(low) and HI(high). In this screen,
press on/off Control Key to enter
the following steps for LO/HI
voltage setting.
B. The cursor (
→ ) will pop up to
indicate the item newly selected.
Press on/off Control Key to get
the item of LO or HI range the
user want to adjust.
C. Use Up or Down-key to adjust
the voltage (changing 1V by
every press). LO (low
rang):176V+/- 20V, HI(high
range):253V+/- 20V).
D. Once the value is confirmed,
press on/off Control Key again to
save the data.
17
10. Output Voltage Set Menu
A. In this screen, press on/off
Control Key to enter the following
steps for output voltage setting.
B. The cursor (
→ ) will pop up to
indicate the output voltage newly
selected.
C. Use Up or Down-key to adjust
the output voltage (220V, 230V,
and 240V are available only).
D. Once the correct voltage is
selected, press on/off Control
Key again to save the data.