PowerWalker VFI 1000E User Manual

Page 9

background image

16

9. Bypass Range Set Menu

A. To protect the load, the function

of bypass auto-transfer is

activated only when the AC main

voltage is within the range of LO

(low) and HI(high). In this screen,

press on/off Control Key to enter

the following steps for LO/HI

voltage setting.

B. The cursor (

→ ) will pop up to

indicate the item newly selected.

Press on/off Control Key to get

the item of LO or HI range the

user want to adjust.

C. Use Up or Down-key to adjust

the voltage (changing 1V by

every press). LO (low

rang):176V+/- 20V, HI(high

range):253V+/- 20V).

D. Once the value is confirmed,

press on/off Control Key again to

save the data.

17

10. Output Voltage Set Menu

A. In this screen, press on/off

Control Key to enter the following

steps for output voltage setting.

B. The cursor (

→ ) will pop up to

indicate the output voltage newly

selected.

C. Use Up or Down-key to adjust

the output voltage (220V, 230V,

and 240V are available only).

D. Once the correct voltage is

selected, press on/off Control

Key again to save the data.