beautypg.com

Specifications – PowerWalker VFI 1000E User Manual

Page 14

background image

26

9. SPECIFICATIONS

Rated Power

Capacity

1KVA / 700W

2KVA / 1400W

3KVA / 2100W

Voltage

Single phase 220Vac, 160~300Vac at 70~100% load

140~300Vac at 50~70% load, 118~300Vac at 0~50% load

Frequency

50Hz or 60Hz +/- 4Hz

Input

Power Factor

≧ 0.95

Voltage, Frequency

Single phase 220Vac +/- 2% (230V or 240V re-settable via

LCD panel), 50Hz or 60Hz

Transient Response

+/- 3% (100% load variation)

Waveform / Distortion

Sine wave, THD < 3% at 0-100% linear load

Output

Crest Ratio

3 : 1

Voltage (longer backup
time is available upon
request)

7Ah / 12V * 3pcs

7Ah / 12V * 8pcs

Battery

Charger

5 hrs to 90% of full capacity after full load discharge

Transfer Time

AC fail 0 ms; 2.5ms typical from inverter to bypass and vice versa

Battery

Battery low shutdown and Fuse

Overload

125~150% 30sec, then switch to bypass and auto

re-transfer; >150% for 200ms

Short Circuit

Current Limited and cut-off and fuse and breaker

Protection

EMI/EMC

EN50091-2

Mains Failure

Beeping every 4 seconds

Battery Low

Beeping once every second

Audible Alarm

Fault, Overload

Continuously

LCD

UPS status, I/P&O/P voltage& frequency, Battery voltage,

Battery capacity, Loading %, Temperature, History record

Indicator

LED

Normal (green), Warning (yellow), Fault (red) LED

DB9 Connector

RS-232 Interface; Power monitoring software (Option)

Communications

SNMP Intelligent Slot

Power management from SNMP manager and Web

browser (Option)

Network

Surge Protection

RJ11 I/O port available for 10 base-T network

or Fax / Modem

Temperature

0-40 degree C; 32-104 degree F

Relative Humidity

0-95% non-condensing

Environment

Acoustic Noise

Less than 45dBA (at 1 meter)

Net Weight (w/o batt.)

7kgs

13.5kgs

14.5kgs

Net Weight (w/ batt.)

14kgs

34kgs

35kgs

Physical

Dimension (WxHxD)mm

160x220x400

200x352x450