6. TROUBLE SHOOTING GUIDE

6.1 UPS Status and Action

The description of the following guideline may be helpful in problem solving.

1. LED and LCD status as below:

UPS STATUS:

AC utility power is normal. UPS is running normally, but battery

capacity is low (referring to Battery Status Menu). Buzzer beeps once

every second for battery low.

ACTION: Charger may broke down. Please replace charger board.

2. LED and LCD status as below:

UPS STATUS:

AC utility power is normal. The output load is supplied through bypass

of AC utility. Fault LED lits up and buzzer beeps continuously.

ACTION: Please contact your agent for service.

19

3. LED and LCD status as below:

UPS STATUS:

AC utility power is normal but UPS is overloaded. Warning LED lits up

and buzzer beeps per second.

ACTION: Please reduce the critical load to POWER(%)<100%.

4. LED and LCD status as below:

UPS STATUS:

AC utility power is normal but UPS is overloaded up to 125%. Warning

LED does not fade out and buzzer beeps per 0.5 second.

ACTION: Please reduce the critical load to POWER(%)<100%.