beautypg.com

Table 2. serial interface programming commands – Rainbow Electronics MAX5515 User Manual

Page 15

background image

MAX5512–MAX5515

Dual, Ultra-Low-Power,

8-Bit, Voltage-Output DACs

______________________________________________________________________________________

15

Table

2. Serial Interface Programming Commands

CONTROL BITS

INPUT DATA

SUB-BITS

C3

C2

C1

C0

D7–D0

S3, S2, S1, S0

FUNCTION

0

0

0

0

XXXXXXXX

0000

No operation; command is ignored.

0

0

0

1

8-bit data

0000

Load input register A from shift register; DAC registers unchanged;
DAC outputs unchanged.

0

0

1

0

8-bit data

0000

Load input register B from shift register; DAC registers unchanged;
DAC outputs unchanged.

0

0

1

1

Command reserved. Do not use.

0

1

0

0

Command reserved. Do not use.

0

1

0

1

Command reserved. Do not use.

0

1

1

0

Command reserved. Do not use.

0

1

1

1

Command reserved. Do not use.

1

0

0

0

8-bit data

0000

Load DAC registers A and B from respective input registers; DAC
outputs A and B updated; MAX5513/MAX5515 enter normal
operation if in standby or shutdown; MAX5512/MAX5514 enter
normal operation if in shutdown.

1

0

0

1

8-bit data

0000

Load input register A and DAC register A from shift register; DAC
output A updated; Load DAC register B from input register B; DAC
output B updated; MAX5513/MAX5515 enter normal operation if in
standby or shutdown; MAX5512/MAX5514 enter normal operation
if in shutdown.

1

0

1

0

8-bit data

0000

Load input register B and DAC register B from shift register; DAC
output B updated; Load DAC register A from input register A; DAC
output A updated; MAX5513/MAX5515 enter normal operation if in
standby or shutdown; MAX5512/MAX5514 enter normal operation
if in shutdown.

1

0

1

1

Command reserved. Do not use.

1

1

0

0

D7, D6,

XXXXXX

0000

MAX5513/MAX5515 enter standby*, MAX5512/MAX5514 enter
shutdown. For the MAX5513/MAX5515, D7 and D6 configure the
internal reference voltage (Table 3).

1

1

0

1

D7, D6,

XXXXXX

0000

MAX5512–MAX5515 enter normal operation; DAC outputs reflect
existing contents of DAC registers. For the MAX5513/MAX5515,
D7 and D6 configure the internal reference voltage (Table 3).

1

1

1

0

D7, D6,

XXXXXX

0000

MAX5512–MAX5515 enter shutdown; DAC outputs set to high
impedance. For the MAX5513/MAX5515, D7 and D6 configure the
internal reference voltage (Table 3).

1

1

1

1

8-bit data

0000

Load input registers A and B and DAC registers A and B from shift
register; DAC outputs A and B updated; MAX5513/MAX5515 enter
normal operation if in standby or shutdown; MAX5512/MAX5514
enter normal operation if in shutdown.

X = Don’t care.
*Standby mode can be entered from normal operation only. It is not possible to enter standby mode from shutdown.