VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA__HART two-wire User Manual

Page 56

background image

D

amping (63 % of the input variable)

0 … 999

s, adjustable

F

ulfilled NAMUR recommendations

NE

43

HART

output values

-

1. HART

value (Primary Value)

D

istance to the level

-

2. HART

value (Secondary Value)

D

istance to the level - scaled (for example hl, %)

R

esolution, digital

>

1

mm (0.039 in)

Input variable

M

easured variable

distance between process fitting and product sur-
face

M

in. distance from antenna end

50

mm (1.969 in)

3)

R

ecommended measuring range, encapsu-

lated antenna system

up to 10 m (32.81 ft)

R

ecommended measuring range plastic horn

antenna

up to 20 m (65.62 ft)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

18 … +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

O

ther reference conditions

-

R

eflector

ideal reflector, e.g. metal plate 2 x 2 m

-

F

alse reflections

L

argest false echo 20 dB smaller than the useful

echo

Characteristics and performance data

F

requency

K-

band (26 GHz technology)

M

eas. interval approx.

1

s

B

eam angle -3 dB

4)

-

E

ncapsulated antenna system

22°

-

P

lastic horn antenna

10°

S

tep response or adjustment time

5)

<

1

s (dependent on the parameter settings)

M

ax. level change

A

djustable up to 1 m/min. (dependent on the

parameter settings)

M

ax. emitted HF power of the antenna system

-

P

ulse peak power

<

2

mW

3)

I

n products with low dielectric value up to 50 cm (19.69 in).

4)

C

orresponds to the range with 50 % of the emitted power

5)

T

ime to output the correct level (with max. 10 % deviation) after a sudden

level change.

56

VEGAPULS

61 • 4 … 20

mA/HART two-wire

10 S

upplement

28434

-EN

-100426