3 mounting instructions – VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA__HART two-wire User Manual

Page 15

background image

must be screwed to the sensor with the three hexagon socket screws
M

5

x 10 and spring washers before setup. Max. torque see chapter

"

Technical data". Necessary tools: Allen wrench size 4.

S

crewing on is possible in two ways. Depending on the selected

version, the sensors can be swivelled in the strap as follows:

l

S

ingle chamber housing

-

180°

infinitely variable

-

in three steps 0°, 90° and 180°

l

D

ouble chamber housing

-

90°

infinitely variable

-

in two steps 0° and 90°

4

.3 Mounting instructions

W

hen mounting the sensor, keep a distance of at least 200 mm

(7.874

in) from the vessel wall. If the sensor is installed in the center of

dished or round vessel tops, multiple echoes can arise. These can,
however, be suppressed by an appropriate adjustment (see chapter
"

Setup").

I

f you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo
storage later with existing buildup.

> 200 mm

(7.87")

Fig. 7: Mounting on round vessel tops

1

Reference plane

2

Vessel center or symmetry axis

Mounting position

VEGAPULS

61 • 4 … 20

mA/HART two-wire

15

4 M

ounting

28434

-EN

-100426